Emerson FB3000 RTU Instruction Manual
D301851X012
May 2022
10
Installation
Figure 2-2: Removing Chassis Connector Cover
2.
Press the two chassis together. If mounting on a DIN rail, slide both chassis onto the DIN rail
first to ensure proper alignment and place clamps/brackets at both ends of assembly on DIN
rail to ensure side connectors between chassis remain fully engaged. (See
Section 2.6
)
.
Figure 2-3: Pressing Chassis Together
2.4
General Wiring Guidelines
The RTU’s pluggable terminal blocks use compression-type terminals that accommodate wire
between 24 and 12 AWG depending on the connector or terminal block and the usage. Use 28 to
16 AWG wires on the 20 pin I/O connectors; use 20 to 12 AWG wires on the power connection.
CAUTION
All wires must be rated for a temperature of 90
o
C or higher.
CAUTION
Wires used for power must have a wire gauge between 20 and 12 AWG.
When making a connection, insert the bare end of the wire (approx. 1/4" max) into the clamp
adjacent to the screw and secure the screw.
To prevent shorts, ensure that no bare wire is exposed. You can also use crimp bootlace
ferrules (18 to 24 AWG for I/O; 18 to 20 AWG for power).
Allow some slack in the wire while making terminal connections. Slack makes the wires more
manageable and helps minimize mechanical strain on the terminal blocks.
Содержание FB3000
Страница 7: ...FB3000 CSA Approval Information CD9411L Issued March 11 2021 CSA 5 ...
Страница 8: ......
Страница 12: ......
Страница 46: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 34 Installation ...
Страница 68: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 56 I O Configuration and Wiring ...
Страница 72: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 60 Operation ...
Страница 94: ......