Emerson FB3000 RTU Instruction Manual
D301851X012
May 2022
38
I/O Configuration and Wiring
Alternatively, you can use loop power as shown in
Figure 3-2
. In the figure, AIDIPI_08 is
shown connected to an external current source.
The current source is powered by the 24V loop supply which can power up to 8 field
devices (4-20mA or 1-5V). To create the correct ground reference, connect the 24V loop
GND (pin 20) externally to ISOGND (in this case pin 10).
Figure 3-2: Analog Input (AI) Wiring Using Loop Power
1
External current source
3.2
Analog Outputs
The FB3000’s mixed I/O modules includes two dedicated analog output channels, with
the following characteristics:
Table 3-3: Analog Output Characteristics
Type
Number Supported
Characteristics
Analog Output
(AO)
2 dedicated channels
4 to 20 mA range (or 1 to 5V)
selectable within FBxConnect.
Both analog outputs share a common
ground.
You disable unused analog outputs to
conserve power.
Содержание FB3000
Страница 7: ...FB3000 CSA Approval Information CD9411L Issued March 11 2021 CSA 5 ...
Страница 8: ......
Страница 12: ......
Страница 46: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 34 Installation ...
Страница 68: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 56 I O Configuration and Wiring ...
Страница 72: ...Emerson FB3000 RTU Instruction Manual D301851X012 May 2022 60 Operation ...
Страница 94: ......