Emerson FB3000 RTU Instruction Manual
D301851X012
May 2022
I/O Configuration and Wiring
53
3.6.1.4
Analog Output Mode (HART Communication Disabled)
If you have an unused HART channel, you can use it as a 4-20mA current sinking analog
output.
In FBxConnect, you must Disable the 250 Ohm Termination Resistor and set the HART
Comm Mode to Disabled.
Figure 3-14
shows two examples for wiring a HART channel as a 4-20mA analog output.
In the figure, an externally powered current loop receiver connects to Channel 1 and a
24VDC loop supply-powered current loop receiver connects to Channel 4.
Figure 3-14: Connecting 4mA to 20mA Analog Outputs to 3HRT04 Channel (No HART communications)
1
4-20mA Analog Signal Loop
2
Transducer
3
Driver
4
Power Supply
5
Actuator
6
3HRT04 Module internal ground connections (for information only; not visible to user)
7
External Power Source