74
September 2020
Service Instructions
MAN-02-08-77-0714-EN Rev. 2
Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
8.5 Alarms
Table 27.
Configuration Table (16)
MENU NAME
MENU
KEY
DEFAULT ACTION
ALARMS
AL
N/A
SOLENOID VALVE ALARM
Alarm will activate when a coil failure in the solenoid has
been detected.
SL
Stay Put
ESD(hardwire, host) function re-
mains active
PRESSURE TRANSMITTER ALARM
Alarm will activate when the signal from the pressure
transmitter has been lost.
Pt
Stay Put
ESD(hardwire, host) function re-
mains active
ENCODER ALARM
Alarm will activate when the signal from the position encoder
has been lost.
Ea
Stay Put
ESD(hardwire, host) function re-
mains active
OVER PRESSURE ALARM
Alarm will activate when the hydraulic pressure of the SMART
EHO exceeds the configured maximum operating pressure.
Alarm will clear when pressure goes below maximum
operating pressure.
PF
Stay Put - Modulating
No Action - On/Off
PARTIAL STROKE TEST FAIL ALARM
Alarm will activate when another alarm occurs during the
partial stroke test, or if the partial stroke test is aborted by the
user remotely or locally.
Pe
Action taken based on Failure Alarm
Stay put when aborted by user until
another command is given
LOST COM1 ALARM
Alarm will activate when the Modbus communication signal is
lost. The alarm is disabled by default and can only be
configured via DCMlink. A loss of Foundation Fieldbus and
HART communcation will not produce an alarm.
ca
No Action
VALVE STALL ALARM
Alarm will activate when SMART EHO fails to move upon
command. If log jam is enabled, the SMART EHO will initiate
log jam sequence. If log jam sequence is unsuccessful in
moving the valve, the Valve Stall Alarm will activate.
Sa
Stay Put
HARDWIRED ESD ALARM
Alarm will activate when ESD event occurs with its
associated ESD signal.
ES
Fail-Safe Position
HOST COMMAND ESD ALARM
Alarm will activate when ESD command is sent over a
communication protocol from the host system to the
SMART EHO. The alarm will remain until the ESD command
is removed.
HE
Fail-Safe Position
PHASE MONITOR ALARM
Alarm will activate when the phase sequence is incorrect. This
only applies to three phase power systems.
Ph
Stay Put