![Emerson Bettis EHO G01001.5 Скачать руководство пользователя страница 71](http://html.mh-extra.com/html/emerson/bettis-eho-g01001-5/bettis-eho-g01001-5_service-instructions-manual_102062071.webp)
67
Service Instructions
MAN-02-08-77-0714-EN Rev. 2
September 2020
Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
Table 22.
Configuration Table (11)
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT
ACTION
ESD CONFIGURATION
Configure the settings for the ESD controls.
Caution: This is a software ESD action. The software
ESD action will be initiated by the software of the
electronics. The hard wired ESD is independent from
the software ESD.
EC
Yes/No
n/a
ENABLE ESD FROM HARDWIRE
Provides indication if hardwire ESD is
enabled or disabled on the SMART EHO.
eH
0 = Disable
1 = Enable
1 = Enable
REDUNDANT ESD DELAY
Delay for triggering Redundant ESD if Hardwired
ESD fails or operates slowly
rE
0 to 60 seconds
0 seconds
ENABLE SOFTWARE ESD FROM
LOST COMMUNICATION
Enable the SMART EHO to go to fail safe position if
Modbus communication link is lost for 5 seconds.
eC
0 = Disable
1 = Enable
0 = Disable
ENABLE ESD FROM HOST
Enable host system to provide a command to take
the Smart EHO to the fail safe position.
eE
0 = Disable
1 = Enable
0 = Disable
SOFTWARE ESD OVERRIDE LOCAL MODE
Enable host system to provide a command
to take the SMART EHO to the fail safe position.
eE
0 = Disable
1 = Enable
0 = Disable
SOFTWARE ESD ACTION
Configure the action to be taken if Enable ESD
from Lost Communication or Enable
ESD from Host is enabled.
eA
0 = Stop / Stay put
1 = Open to Limit
2 = Close to Limit
Feedback Only
SOFTWARE ESD OVERRIDE LOCAL MODE
Configure the SMART EHO to allow the host to
override LOCAL mode control with a software
ESD command.
WARNING: Enabling this would allow
the actuator to move during a software
ESD command.
eL
0 = NO
1 = YES
1 = YES
SOFTWARE ESD OVERRIDE STOP MODE
Configure the SMART EHO to allow the host to
override STOP(OFF) mode control with a software
ESD command.
WARNING: Enabling this would allow the actuator
to move during a software ESD command.
eS
0 = NO
1 = YES
1 = YES
SOFTWARE ESD OVERRIDE MOTOR
THERMAL ALARM
Configure the SMART EHO to allow the host to
override a Motor Thermal Alarm with a software
ESD command.
et
0 = NO
1 = YES
1 = YES
ESD OVERRIDE INHIBIT
Configure the Smart EHO to allow the host
to override Inhibit command with a software
ESD command.
ei
0 = NO
1 = YES
1 = YES