Service Instructions
MAN-02-08-77-0714-EN Rev. 2
September 2020
Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
Table 18.
Configuration Table (7)
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT ACTION
RELAY3 SETTING
Configure Relay3 to provide
either a continuous or flashing
signal if Relay3 Function is met.
Flashing will be in 1 second
intervals.
S3
0 = Continuous
1 = Flashing
0 = Continuous
RELAY4 FUNCTION
Set SMART EHO's configurable
relays to provide various
actuator status indication.
Note: Partial Stroke Test(21) FAIL
indication will be available on
this relay only.
Note: Generic (Host Control) -
Host can activate, deactivate, or
control the relay.
r4
0 = Limit Switch Open (LSO)
1 = Limit Switch Close (LSC)
2 = Limit Switch A (LSA)
3 = Limit Switch B (LSB)
4 = Opening
5 = Closing
6 = Local Mode
7 = Stop Mode
8 = Remote Mode
9 = Valve Drift Alarm
10 = Power Monitor Alarm
11 = Phase Monitor Alarm
12 = Motor Thermal Alarm
13 = Hardwired ESD Alarm
14 = ESD Active Alarm
15 = Lost Analog Input 1 Alarm
16 = Generic (Host Control)
17 = Electronic Fault Alarm
18 = Moving
19 = Valve Stall Alarm
20 = PST-(Partial Stroke Test)
21 = Actuator Fail Alarm
22 = Unit Alarm
23 = SOV Failure Alarm
24 = Hydraulic Circuit Failure Alarm
25 = Self-Calibration Failure Alarm
26 = Over Pressure Alarm
27 = Emergency Stop Alarm
28 = Host Command ESD
1 = Limit Switch
Close (LSC)