Service Instructions
MAN-02-08-77-0714-EN Rev. 2
September 2020
Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
Table 13.
Configuration Table (2)
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION
VALUE
DEFAULT
ACTION
LOCAL CONTROL
Set the SMART EHO's local control OPEN/
CLOSE selector switch to momentary or
maintained. Momentary is described as a
quick toggle of the OPEN/CLOSE selector
knob will complete the stroke. Maintained is
described as holding the OPEN/CLOSE
selector knob to complete the stroke. If the
OPEN/CLOSE selector knob is released, the
actuator will stop the travel.
Lc
0 = Momentary
1 = Maintained
0 = Momentary
REMOTE CONTROL
Set the SMART EHO's remote controls to
momentary or maintained. Only applicable to
discrete signals. A discrete remote input signal
will cause the actuator to complete a full
stroke. Only a discrete stop input signal will
stop the travel. The direction of the actuator
can be reversed by a discrete remote signal in
the opposite direction.
rc
0 = Momentary
1 = Maintained
0 = Momentary
WRITE PROTECT
By enabling write protect, the user can
prevent the actuator from configuration
changes through HART and Foundation
Fieldbus communication.
ro
0 = Disable
1 = Enable
0 = Disable
POSITION CONTROL BANDWIDTH
Sets the minimum resolution.
Pb
0.5 to 5.0
0.6 (%)
(Modulating)
2.0(%)(On/Off)
ENABLE SETPOINT TRACKING
Enable or disable setpoint tracking feature.
Et
0 = Disabled
1 = Enabled
0 = Disabled
LIMIT SWITCH TRIGGER POINT A
Set the SMART EHO's limit switch range. The
limit switch will be triggered between 0% and
the limit switch trigger setpoint. Any position
greater than the limit switch trigger setpoint,
the limit switch will be triggered off. 0% will be
designated as [C][L] on the two-digit display
and 100% will be designated as [O][P] on the
two-digit display.
La
0 - 100
The values 0 and 100
would be displayed as
[O][P] for Open and [C]
[L] for Close
25(%)