71
Service Instructions
MAN-02-08-77-0714-EN Rev. 2
September 2020
Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
Table 24.
Configuration Table (13)
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT
ACTION
PARTIAL STROKE TEST (PST)
PA
Yes/No
N/A
ENABLE PST
Enable the PST on the EHO.
PE
0 = Disable PST
1 = Enable PST
0 = Disable
PST
PST START POSITION
Configure the position where the PST will start
the test.
PP
0 = Fail-safe position
1 = Power stroke position
1 = Power
stroke
position
PST TRAVEL RANGE
Configure the percent range the EHO will stroke
the valve during the partial stroke test.
tr
1(%) to 30(%)
30(%)
PST PAUSE TIME
Configure the time the EHO will pause at the
position at the of the partial stroke test before
returning to the position prior to initiating the
partial stroke test.
Po
1(s) to 30(s)
5(s)
START PST
Initiate the local partial stroke test using
the LDM.
PL
Yes/No
N/A
PST STARTED
Status signal on the two digit display to inform
the user PST is in progress.
Pe
N/A
Feedback
Only
PST Status
PST PASSED
Status signal on the two digital display to inform
the user PST has passed.
P1
N/A
Feedback
Only
PST Passed
PST FAILED
Status signal on the two digital display to inform
the user PST has failed.
P2
N/A
Feedback
Only
PST Failed
INHIBIT
in
Yes/No
N/A
ENABLE INHIBIT CLOSE
Configure Discrete Input 5 to accept a discrete
24 V DC signal to inhibit close. If Discrete Input 5
is provided a 24 V DC signal when inhibit close is
enabled, close commands will not be functional.
If Discrete Input 5 is not provided a 24 V DC signal
when inhibit close is enabled, remote close
commands will be functional.
ic
0 = Disable
1 = Enable
0 = Disable
ENABLE INHIBIT OPEN
Configure Discrete Input 4 to accept a discrete
24 V DC signal to inhibit open. If Discrete Input 4
is provided a 24 V DC signal when inhibit open is
enabled, open commands will not be functional.
If Discrete Input 4 is not provided a 24 V DC signal
when inhibit open is enabled, remote open
commands will be functional.
io
0 = Disable
1 = Enable
0 = Disable