Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT
ACTION
CALIBRATE UPPER LIMIT FOR ANALOG INPUT CHANNEL
Calibrate the the analog input channel with an external
current source. External current source needs to be
connected to source 20 mA equivalent signal when this
menu is being flashed. The signal has to be in the range
3.6 mA - 22 mA.
iU
Yes/No
N/A
UPPER LIMIT VALUE CALIBRATED
(CALIBRATION STATUS)
If the input value is valid, the device will return success.
cU
N/A
Analog Input
Calibration Status.
Not Searchable/
Configurable
CALIBRATION FAILED (CALIBRATION STATUS)
If the input value is invalid, the device will return fail. The
SMART EHO will maintain the previous calibrated value.
cF
N/A
Analog Input
Calibration Status.
Not Searchable/
Configurable
ANALOG OUTPUT 1 CALIBRATION
Calibrate Analog Output 1 Channel
o1
Yes/No
N/A
CALIBRATE LOWER LIMIT OF ANALOG OUTPUT 1
Calibrate the Analog Output 1 Channel for 4 mA
equivalent value. The Channel Output needs to be
monitored externally.
oL
Yes/No
N/A
ANALOG OUTPUT 1 CALIBRATION CHOICE
Select if the Analog Output 1 needs to be
increased or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 1
The Analog Output can be changed based on selection
at cC menu. 'Yes' option at this menu means Accept
the Output. 'No' option at this menu will Increase or
Decrease the Output.
c1
Yes/No
N/A
LOWER LIMIT CALIBRATED (CALIBRATION
STATUS)
The Analog Output 1 channel is calibrated for the
desired output.
cL
N/A
Analog Input
Calibration Status.
Not Searchable/
Configurable
CALIBRATION FAILED (CALIBRATION STATUS)
Calibration for Analog Output 1 channel has failed.
The SMART EHO will maintain the previous
calibrated value.
cF
N/A
Analog Input
Calibration Status.
Not Searchable/
Configurable
CALIBRATE UPPER LIMIT OF ANALOG OUTPUT 1
Calibrate the Analog Output 1 Channel for 20 mA
equivalent value.
Note: The channel output needs to be monitored externally.
oU
Yes/No
N/A
ANALOG OUTPUT 1 CALIBRATION CHOICE
Select if the Analog Output 1 needs to be
increased or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 1
The analog output can be changed based on selection at
[c][C] menu. 'Yes' option at this menu means the output
is accepted. 'No' option at this menu will increase or
decrease the output.
c1
Yes/No
N/A
UPPER LIMIT CALIBRATED(CALIBRATION STATUS)
The Analog Output 1 channel is calibrated for the
desired output.
cU
N/A
Analog Output 1
Calibration Status.
Not Searchable/
Configurable
CALIBRATED FAILED (CALIBRATION STATUS)
Calibration for Analog Output 1 channel has failed.
The SMART EHO will maintain the previous
calibrated value.
cF
N/A
Analog Output 1
Calibration Status.
Not Searchable/
Configurable
ANALOG OUTPUT 2 CALIBRATION
Calibrate Analog Output 2 Channel
o2
Yes/No
N/A