Section 8: Customizing Smart EHO Settings
Customizing Smart EHO Settings
MENU NAME
MENU
KEY
CONFIGURATION/
CALIBRATION VALUE
DEFAULT
ACTION
CALIBRATE LOWER LIMIT OF ANALOG OUTPUT 2
Calibrate the Analog Output 2 Channel for 4 mA
equivalent value. The channel output needs to be
monitored externally.
oL
Yes/No
N/A
ANALOG OUTPUT 2 CALIBRATION CHOICE
Select if the Analog Output 2 needs to be increased
or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 2
The Analog Output can be changed based on selection
at [c][C] menu. 'Yes' option at this menu means accept
the output. 'No' option at this menu will increase or
decrease the output.
c2
Yes/No
N/A
CALIBRATION PASSED FOR LOWER LIMIT
(CALIBRATION STATUS)
The Analog Output 2 channel is calibrated for the
desired output.
cL
N/A
Analog Output 2
Calibration Status.
Not Searchable/
Configurable
CALIBRATED FAILED (CALIBRATION STATUS)
Calibration for Analog Output 2 channel has failed.
The SMART EHO will maintain the previous
calibrated value.
cF
N/A
Analog Output 2
Calibration Status.
Not Searchable/
Configurable
CALIBRATE UPPER LIMIT OF ANALOG OUTPUT 2
Calibrate the Analog Output 2 Channel for 20 mA
equivalent value. The channel output needs to be
monitored externally.
oU
Yes/No
N/A
ANALOG OUTPUT 2 CALIBRATION CHOICE
Select if the Analog Output 2 needs to be increased
or decreased.
cC
0 = Increment
1 = Decrement
0 = Increment
CALIBRATING ANALOG OUTPUT 2
The Analog Output can be changed based on selection
at [c][C] menu. 'Yes' option at this menu means accept
the output. 'No' option at this menu will increase or
decrease the output.
c2
Yes/No
N/A
CALIBRATION PASSED FOR UPPER LIMIT
(CALIBRATION STATUS
)
The Analog Output 1 channel is calibrated for the
desired output.
cU
N/A
Analog Output 2
Calibration Status.
Not Searchable/
Configurable
CALIBRATED FAILED (CALIBRATION STATUS)
Calibration for Analog Output 2 channel has failed.
The SMART EHO will maintain the previous
calibrated value.
cF
N/A
Analog Output 2
Calibration Status.
Not Searchable/