Device Communicator Plus communication module
Figure 2-5:
A.
Power a FOUNDATION fieldbus device. You need to connect the FOUNDATION fieldbus Power Plug
to the FF pwr and the positive FF terminals.
B.
Connect to a FOUNDATION fieldbus device that is externally-powered or powered by the Trex unit.
C.
Measure current on a 4-20 mA current loop.
D.
Power and connect to a HART device. The HART+pwr terminals can measure the current output of a
connected transmitter or control the current input to a connected positioner. The terminals also
have a loop resistor for device communication.
E.
Connect to an externally-powered HART device. The HART terminals also have an optional loop
resistor for enabling HART communications on 4-20 current loop and optional current control for
moving a positioner.
CAUTION!
•
Before you insert or remove a communication module, ensure the Trex unit is powered
off.
•
Ensure sufficient grounding. Ensure the personnel, working surfaces, and packaging are
sufficiently grounded when handling electrostatically sensitive parts.
•
Avoid touching the pins on the connectors or components. Discharged energy can affect
the modules.
•
When you insert/attach the communication module to the Trex unit, do not over tighten
the screws. Use 0.5Nm maximum torque load.
•
Remove the USB cable from the Trex unit before connecting to a device.
AMS Trex Device Communicator overview
User Guide
11
Содержание AMS Trex
Страница 1: ...User Guide Rev 3 August 2017 AMS Trex Device Communicator User Guide ...
Страница 8: ...Contents vi User Guide ...
Страница 130: ...Field Communicator application 122 User Guide ...
Страница 186: ...Fieldbus Diagnostics application 178 User Guide ...
Страница 198: ...Technical specifications 190 User Guide ...
Страница 206: ...Glossary 198 User Guide ...