Installation
page 52
ELTROPLAN-REVCON
Terminals 5 and 6
These terminals are already used for the internal temperature supervision of the
heat sink.
Terminals 7 and 8
(use screened wires only, max length)
OFF
-signal
These terminals may be used for an external
OFF
-signal (NOC, short time
contact) to stop the power feedback unit.
Note!
The OFF-signal stops the backfeeding immediately. If this is done in regen
mode, the controller would trip because of too high DC-bus voltage right
afterwards.
Terminal 11 and 12
(used screened wires only)
These terminals may be used for an external
ON
-signal (external voltage 12 –
24V DC [e.g. from PLC], short time pulse) to start / reset the power feedback
unit.
(connect „Plus“ to terminal 11, „Minus“ to terminal 12)