Configuration
ELTROPLAN-REVCON
page 63
STOP!
Pull off the jumper J3 is only allowed by interrupting the pulses of the
frequency inverter or of the power feedback unit in the case of switching
off the mains by series interrupting devices like contactors, main switches
or any others. This is necessary to stop the power feedback to prevent a
dangerous voltage rise on devices in the sector where the power is
switched-off. The Jumper J7 should only be removed in the case of
Jumper J3 is removed. Otherwise when the phase-failure-supervision is
active a "phase failure" will only be shown as long as the failure is existing
(no error storage).
f) Overvoltage supervision
Since the control board version 1.4.3 the device has an overvoltage supervision
for the mains which switches off the device in the case of a voltage level of
approximately 1,15 x U
N
and above. As an error message the error code 3 will
be shown (see chapter 7.1). For the differentiation of the error messages phase
failure and overvoltage you have the possibility to deactivate the phase-failure-
supervision by removing the jumper J3 on the control board. If after that a
switch-off with the indication via the red and yellow LED (error code 3) hap-
pens, an overvoltage will be the reason of the switch-off then.
J3 J5 J6 J7 J8 LED Message
evaluation (overvoltage)
— X X — — Green 1.red yellow overvoltage a/o phase failure/commutation error
— X X 0 — green —
yellow overvoltage
0 X X — — green 1.red yellow overvoltage a/o phase failure/commutation error
0 X X 0 — green —
yellow overvoltage
0 X X 0 — green 1.red yellow constant phase failure
Remark:
0
Jumper open
—
Jumper closed
X
Jumper random
Standard adjustment of the device
Autostart and no switching off in case of phase failure
STOP