Safety information
page 12
ELTROPLAN-REVCON
•
The warranty given by us expires, if the unit is modified or (even partially)
dismantled or if it is used in contradiction to our instructions.
•
The constructor of the plant, who has to know the technical guidelines,
bears the responsibility for the correct selection and arrangement of the
electrical components.
•
Putting into operation of the power feedback unit is only admissible at
VDE-conform nets of electrical power supply. Non observance may dam-
age the device!
•
In accordance with the corresponding standards and guidelines the opera-
tion on even for a short time over-compensated networks (cos
ϕ≤
1) respec-
tively on un-choked compensation-units is not admissible. If this is done
nevertheless, overvoltages will occur (caused by oscillating currents),
which may damage all connected components, especially electronic units
like controllers and power feedback units.
•
To low powered or unloaded generators and to regulating transformers it is
never allowed to feed back power without a previous consultation of our
application department. Otherwise unintended voltage rises / excess volt-
ages are generated, which may damage or destroy REVCON
and com-
bined units!
•
Before operating at nets without reference to neutral ground additional
safety measures (e.g. installation of over voltage suppressors like MOV’s)
have to be done. If necessary, please ask for technical support by our tech-
nicians.
•
An undisturbed operation of the power feedback unit is only probable, if
the following instructions are observed. If these instructions are not ob-
served, tripping of the unit and damages may occur.
♦
Pay attention to the correct values of mains and DC-bus voltage.
♦
Separate power and control wires (> 15cm)
♦
Use shielded or twisted control wires. Connect both ends of the
shield to ground!