Configuration
page 62
ELTROPLAN-REVCON
d) Reset
After the failure is removed, a stored error has to be reset by pushing the
RESET-button or rather by switching-off and on again the main circuit voltage
(3-ph.)
Stop!
A reset in case of too high DC-bus voltage during the braking operation is
not recommend. If it is done nevertheless, the power semiconductors are
exposed to increased stress, which may lead to accelerated aging.
e) „Phase failure“
The phase-failure-supervision monitors the mains supply in all 3 phases.
In case of a breakdown of one phase the unit stays still in function, but with
reduced feedback power.
The power feedback unit reacts in different ways on phase failures. One possi-
bility is the "2 phase operation", the other one let the system get out of opera-
tion and the collective-error-relay signals the failure.
Coding via jumper, see figure 4.4.4.1.1:
J3 J5 J6 J7 phase-failure-supervision
— 0
0
— sensitive, error storage "ON"
0
Jumper open
— — — — insensitive, error storage "ON"
—
Jumper closed
0
X
X
— off, but error storage "ON"
X
Jumper random
0
X
X
0
off, error storage "OFF"
Remark: Jumper J7 is only existing from version 1.4.2 of the control board. Error stor-
age "ON" means that the error "phase failure" is shown via LED until you con-
firm. Error storage "OFF" how-ever means that the error "phase failure" is
shown via LED only as long as the failure is really existing.
STOP