23
Functional principle of the joker² light barrier system
Copyright eltima electronic 2022
Release time
Name:
rel time
, Levels:
,
,
,
Default setting: 250 ms
The release time determines the time for which the switches of an output
are closed after a trigger. During this time, both switches are always closed
at the same time.
range
unit
step
0- 8800
µs
200 µs
0 - 9999
ms
1 ms
0 - 3600
s
1 s
0 - 60
min
1 min
Release period
Name:
rel peri
, Levels:
,
,
,
Default setting: 350 ms
An output can also switch several times after a trigger. The release period is
the time from the start of one release to the start of the next release.
Since the release period, as defined above, includes the release time, the re-
lease period must be at least as long as the release time. This condition is
ensured by the software. If the release time is changed to a value greater
than the release period, the value of the release period is automatically in-
creased by the software to the same value as the release time. However if
the release time is decreased, the value of the release period will not be ad-
justed!
In the case of multiple releases, always set this parameter to a value
greater than the release time. If the parameters have the same value,
a multiple release will become one long release instead!
range
unit
step
0- 8800
µs
200 µs
0 - 9999
ms
1 ms
0 - 3600
s
1 s
0 - 60
min
1 min