82
www.elspec-ltd.com | December 2014 | SMX-0609-0101
User Manual | EQ-ST | V15
M
EASUREMENT
T
EST
The L C M Test is not being displayed:
(1)
The Loads value should remain almost the same value regardless whether or not the capacitors
are connected;
(2)
The Caps value should indicate the kVAr value of the connected group as a minus value;
(3)
The Mains value should approximately equal the Loads value minus the Caps value;
(The Caps & Loads indicators are located opposite the [W] firmware).
Should any of the aforementioned points be absent, the cause may be due to:
(1)
The power supplying the system is not at the correct phase order, & / or
(2)
The power supplying the system is not in the phase as that of
s, & / or
(3)
The Mains
incorrectly, & / or
(4)
The polarity of the Mains
, & / or
(5)
The CT ratio on the controller itself has been setup incorrectly;
Issues due to changes made to the external system
Elspec has concluded their final testing procedure:
(1)
The CT ratio in the system is setup incorrectly;
(2)
The system or Cap CT s are incorrectly connected;
(3)
The polarity the system CT s is reversed;
(4)
The
phases are not synchronized with the Mains CT s phases;
Содержание EQUALIZER-ST
Страница 1: ...1 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V16 16 ...
Страница 99: ...99 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 3 PHASE DELTA CONFIGURATION ...
Страница 100: ...100 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 ...
Страница 101: ...101 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 SINGLE PHASE CONFIGURATION ...