61
www.elspec-ltd.com | December 2014 | SMX-0609-0101
User Manual | EQ-ST | V15
Figure 74 - LCM Screen With Caps
Correct Measurement Readings:
□
The new loads will increase simultaneously (to a slighter degree) with increase in compensation,
voltage & power;
□
The Caps (negative value) will display the size of the connected groups;
□
The correct Main value needs to equal the Load Size minus
Once you have completed the Testing Procedure & verified that all the system reads the correct
measurements, you may set the Controller to
CAUTION
Refer to the Troubleshooting Chapter should the
measurements differ or read incorrectly. DO NOT SET THE
CONTROLLER TO AUTOMATIC MODE UNTIL THE
MEASUREMENTS ARE CORRECT.
Controller
F
RONT
P
ANEL
Header;
Main Display;
Function keys and tags;
The functions of the first and last items are as described in the sections below.
!