Figure 3: Controller
The controller performs two major functions:
C
ONTROL
The control function of the controller constantly samples the currents and voltages and analyses the precise
capacitor groups required to obtain an accurate power factor or kVAr. This function uses a unique real-time
load variation analysis for accurate analysis within approximately 1 millisecond.
In addition, the control function runs system tests to analyze unit condition, provide malfunction indications
and adjust unit operation as required.
The controller generates precise firing pulses for the switching module as required to connect or disconnect
capacitor groups.
M
EASUREMENT
The controller features advanced measurement capabilities, including harmonic analysis and waveforms.
Readings are provided for three sections (Figure 4):
Mains reading as indicated by the
M
symbol, displaying the measurement of the total network including
the compensation system.
Load center reading as indicated by the
L
symbol, displaying the measurement of the load without the
compensation system.
Capacitor system reading as indicated by the
C
symbol, displaying the measurement of the system only.
Содержание EQUALIZER-ST
Страница 1: ...1 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V16 16 ...
Страница 99: ...99 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 3 PHASE DELTA CONFIGURATION ...
Страница 100: ...100 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 ...
Страница 101: ...101 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 SINGLE PHASE CONFIGURATION ...