81
www.elspec-ltd.com | December 2014 | SMX-0609-0101
User Manual | EQ-ST | V15
Figure 90: Group Details Screen - Group OK
When Group #1 information is displayed, pressing F5 (
) will display background readings (
). This is
the system internal kVAr readings when all the capacitor groups are disconnected. Normally, all values should be
zero. However, if one of the groups is malfunctioned with a burned SCR, it may cause a short circuit and turn on a
group (or all or part of the phases) and the kVAr readings will be non-zero. This will also cause E3 on this group.