63
www.elspec-ltd.com | December 2014 | SMX-0609-0101
User Manual | EQ-ST | V15
The Status line is displayed below the Capacitor Groups Status. This line will not be shown while menus are
displayed.
The Status line comprises three sections, listing the controller model number, current mode of operation, and
time.
System Mode of Operation may be one of the following:
INSTALL
Site Installation Procedure incomplete; the system requires installation (Page 26).
WARM UP
The system is warming up (after power-on), with all capacitors disconnected. After the 10-
second warm-up period, the system will resume normal operation.
TESTING
The system is testing the capacitor groups.
RUNNING
The system is in Automatic mode of operation and will connect or disconnect groups
automatically.
MANUAL
The system is in Manual mode of operation. Connection or disconnection of groups is
manually performed by the operator.
PAUSED
The system is inhibited by a remote signal (Page 51).
ERROR #
The controller has found an error in the system and disconnected all the groups. For more
details, press F2 (INFO or IN/OUT). See
troubleshooting.
F
UNCTION
K
EYS AND
T
AGS
All controller functions are accessible from five function keys at the bottom of the front panel. The keys' functions
may change and their current function is displayed on the bottom of the screen, by the function keys tags.
Three different display modes are available:
Numeric display, comprising three large-set numbers with minimum and maximum values for the current
measurement;
Graphic display, comprising waveforms or harmonics' bars;
Text display, comprising menus, system information, energy meters or events.
Table 6 summarizes the various functions of the keys in each display mode and sub-mode. The function of F2
Note that in Energy Meters display mode (see Page 74), key functions are identical to those in Numeric Display
mode.
Key
Display
Tag
Function
Page
F1
Numeric
M
ODE
Opens the operation mode set up screen
Graphic
M
ODE
Opens the operation mode set up screen
Содержание EQUALIZER-ST
Страница 1: ...1 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V16 16 ...
Страница 99: ...99 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 3 PHASE DELTA CONFIGURATION ...
Страница 100: ...100 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 ...
Страница 101: ...101 www elspec ltd com December 2014 SMX 0609 0101 User Manual EQ ST V15 SINGLE PHASE CONFIGURATION ...