119
www.elspec-ltd.com | December 2014 | SMX-0609-0101
User Manual | EQ-ST | V15
S
TATUS
&
C
ONTROL
V
ARIABLES
Parameter
Address
Read (R) / Write
(W)
Format
Notes
System
Status
0x2AB4
R
16 Bit
0 = System OK. See
details below -
Table 12: MODBUS Status & Control Variables
S
YSTEM
S
TATUS
B
ITS
:
Bit
Parameter
Values
Bit 0
Operation mode
0=Auto, 1=Manual
Bit 1
Stand-By mode
0=Running, 1=Stop
Bit 2
Installation
0=Completed 1=not yet
Bit 3
Test Status
0=No test 1=Test in Progress
Bit 4
Faults
0=No Faults 1=some general faults
Bit 5
Inhibiting signal
0=Not Activated 1=Activated
Bit 6
Cooling mode
0=Not Activated 1=Activated
Bits 7-15
RESERVED
Table 13: MODBUS Status Bits
P
ARAMETERS
A
DDRESSES
r, s, t
L1, L2 and L3
rs, st, tr
L12, L23 and L31
I
Current
V
Voltage
Number 1
Mains
Number 2
Caps
Number 3
Load
P
Active Power
Q
Reactive Power
S
Apparent Power
Cos
Power Factor
THDI
THD Distortion at Current
THDV
THD Distortion at Voltage
n
Neutral
H1
Harmonics