Setting the parameters
Nunio KNX M-T push button
• Version: 25.02.2021 • Technical changes and errors excepted.
Now specify what should be sent when the control is blocked.
On release, the control variable follows the rule again.
In case of a common control variable for heating and cooling, 0 is always transmitted
as a fixed value.
9.4.3. Fan Coil Control
The fan coil control enables the regulation of the fan of convector heating/cooling sys-
tems.
Activate the fan coil control.
In fan coil control, the fan is automatically controlled by one or, in multi-level systems,
several control variables for heating or cooling. Select which actuating variable(s) are
to control the output. The selection depends on the type of heating/cooling control and
the settings made for the actuating variables.
Select whether the first fan level should also be on when the second and third level are
running and whether the second fan level should also be on when the third level is run-
ning.
Set which mode is to be active after a reset.
When blocked, the control variable shall
• not be sent
• send a specific value
Value (in %)
(if a value is sent)
0...100
Use fan coil control
No •
Yes
Output is controlled via actuating variable
• Heating 1
• Heating 2
• Cooling 1
• Heating 1 and cooling 1
• Heating 2 and cooling 1
• Heating 1 and cooling 2
• Heating 2 and cooling 2
Switch Level 1 on also with Level 2 and 3
No • Yes
Switch Level 2 on also with Level 3
No • Yes
Mode after reset
• Manual
• Automatic (e.g. controller actuating varia-
ble)
Manual stage after reset
(only for manual)
0 • 1 • 2 • 3