26
Setting the parameters
Nunio KNX M-T push button
• Version: 25.02.2021 • Technical changes and errors excepted.
Standby setpoint
Standby mode is usually used for daytime mode when people are absent.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
Eco setpoint
Eco mode is usually used for night mode.
If setpoint values are entered separately:
A starting setpoint value is defined as well as a temperature range in which the setpoint
value may be changed.
If the comfort setpoint value is used as a basis:
If the comfort setpoint value is used as a basis, the reduction/increment of the value is
set.
Starting heating setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 180
Starting cooling setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 240
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 30
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 30
Starting heating setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 160
Starting cooling setpoint (in 0.1 °C)
valid until 1st communication
-300…800; 280
Min. object value heating/cooling
(in 0.1 °C)
-300…800; 160
Max. object value heating/cooling
(in 0.1 °C)
-300…800; 280
Reduce heating setpoint (in 0.1°C)
(for heating)
0…200; 50
Increase cooling setpoint (in 0.1°C)
(for cooling)
0…200; 60