22
Setting the parameters
Nunio KNX M-T push button
• Version: 25.02.2021 • Technical changes and errors excepted.
The
minimum and maximum readings
can be saved and sent to the bus. Use the
"Reset temperature min/max. value" objects to reset the values to the current readings.
The values are not retained after a reset.
9.4.
Temperature PI control – Independent
controller
Activate the control.
Determine if this device should take over the temperature control (stand-alone control-
ler), or if the Nunio display should act as an extension for operating another controller.
The settings for the ‘Stand-alone controller’ option are described below. For configu-
ration as an extension, please see Chapter 9.5.
Temperature PI control – Controller ex-
General control
Set, in which cases
setpoint values and extension time
received via object are to
be retained. The parameter is only taken into consideration if the setting via object is
activated below. Please note that the setting "After power supply restoration and pro-
gramming" should not be used for the initial start-up, as the factory settings are always
used until the 1st communication (setting via objects is ignored).
For an adequate regulation of the ambient temperature, comfort, standby, eco and
building protection modes may be used.
Comfort
when present,
Standby
during short absences,
Eco
as a night-time mode and
Frost/heat protection
(building protection) e. g. with the window open.
The settings for the temperature control include the setpoint temperatures for the in-
dividual modes. Objects are used to determine which mode is to be selected. A change
of mode may be triggered manually or automatically (e.g. by a timer, window contact).
Use minimum and maximum value
No • Yes
Use control
No • Yes
Intended as a
•
Stand-alone controller
• Controller extension (for operating a
stand-alone controller only)
Maintain the
Target values and extension time received
via communication objects
• never
• after power supply restoration
• after power supply restoration and
programming