Setting the parameters
Nunio KNX M-T push button
• Version: 25.02.2021 • Technical changes and errors excepted.
Set the output send pattern.
Block
If necessary, activate the block for the logic output and set what a 1 or 0 at the block
input means and what happens in the event of a block.
Monitoring
If necessary, activate the input monitoring. Set which inputs are to be monitored, at
which intervals the inputs are to be monitored and what value the "monitoring status"
should have, if the monitoring period is exceeded without a feedback being given.
9.8.2. OR LOGIC connection inputs
The OR logic connection inputs are the same as those for the AND logic. Additionally,
the following inputs are available for the OR logic:
Transmission behaviour
• on change of logic
• on change of logic to 1
• on change of logic to 0
• on change of logic and periodically
• on change of logic to 1 and periodically
• on change of logic to 0 and periodically
• on change of logic + object receipt
• on change of logic + object receipt
and cyclically
Send cycle
(if sent periodically)
5 s • 10 s • ... • 2 h
Use block
No • Yes
Assessment of the block object
• At value 1: block | At value 0: release
• At value 0: block | At value 1: release
Blocking object value before first Commu-
nication
0 • 1
Output behaviour
when blocking
• Do not send message
• Send block value [see above,
output value if block active]
when released
(with 2 second release delay)
[send value for current logic status]
Use input monitoring
No • Yes
Input monitoring
• 1 • 2 • 3 • 4
• 1 + 2 • 1 + 3 • 1 + 4 • 2 + 3 • 2 + 4 • 3 + 4
• 1 + 2 + 3 • 1 + 2 + 4 • 1 + 3 + 4 • 2 + 3 + 4
• 1 + 2 + 3 + 4
Monitoring period
5 s • ... • 2 h; 1 min
Output behaviour on exceeding the moni-
toring time
• Do not send message
• Send value exceeding [= value of the
parameter "Monitoring period"]