35
F. Electronics keep sparking
while the pilot burner is ignited
G. Pilot burner is burning, but
magnetic valve closes after ca.
10 seconds or when the appli-
ance gets hot
H. There are short sound
sig- nals, but no sparks and no
sound / clicks can be heard of
the magnet opening the valve
I. Pilot burner is burning, but
there is no gas flow to the main
burner
J. Main burner ignites, but
goes out again after approx. 22
seconds
1. Receiver is damaged.
1. Thermocouple does not function.
2. Batteries (almost) empty.
1. Batteries (almost) empty.
1. Button A in position MAN.
2. Appliance in the pilot flame position.
3. Pre-pressure of the gas is too low.
4. Damaged magnetic valve.
1. Wiring of 2nd thermocouple* is loose.
2. Wires of 2nd thermocouple* have
been cross-connected.
3. Short-circuit in the wiring of thermo-
couple
4. Broken wire in the wiring of 2 nd ther-
mocouple*
5. Thermocouple is dirty.
6. 2 nd Thermocouple* is not positioned
correctly in the flame
7. Thermocouple is defective.
8. Receiver is defective.
* Vesuvius 140 only
1. Replace the receiver and confirm the
code
(remedy 1 at A)
1.1 Measure the voltage, using a digital
mul- timeter, set to mV range, by connect-
ing the cables to the cable shoe. The cable
shoe is located on the outside, directly next
to the magnet nut at the rear of the gas
control;
The voltage should be at least 5mV within
20 seconds.
It may not be lower when the appliance is
warm.
If the voltage is too low:
- the thermocouple should be placed bet-
ter in the flame or
- the thermocouple should be replaced.
1.2 Check the size of the pilot burner
flame.
Correct a flame that is too small.
1.3 Check the wiring of the thermocouple
to the receiver.
If necessary, replace the wiring.
2. Replace the receiver’s batteries.
!Caution Avoid short circuit between the
batteries and metal parts of the appliance.
1. Replace the receiver’s batteries.
!Caution Avoid short circuit between the
batte- ries and metal parts of the appli-
ance.
1. Turn button A on the gas control to ON
2. Increase the flame height by pressing
button (large flame) on the remote control.
3. Check pre-pressure.
If necessary, contact gas company.
4. Replace the gas control.
1. Connect the wiring properly.(figure 2)
2. Connect the wiring properly. (figure 2)
3. Replace wiring.
4. Replace wiring.
5. Clean the thermocouple.
6. Position the thermocouple correctly in
the flame.
7. Check the voltage across thermocou-
ple just before the main burner goes out.
If the voltage is lower than 1.8 mV, re-
place thermocouple
8. Check the voltage across thermocou-
ple just before the main burner goes out.
If the voltage is higher than 1.8 mV, re-
place the receiver.
“Problem”
“Possible cause”
“Remedy”
TROUBLE SHOOTING
Содержание vesuvius 100
Страница 15: ...15 INSTALLER INFORMATION...
Страница 16: ...16 INSTALLER INFORMATION...
Страница 17: ...17 INSTALLER INFORMATION...
Страница 18: ...18 INSTALLER INFORMATION...
Страница 19: ...19 INSTALLER INFORMATION 22 USVK 100 130 REDUCER 130 100 23 USDHC 130 HORIZONTAL TERMINAL 130...
Страница 20: ...20 INSTALLER INFORMATION 24 USBI 100 130 Elbow 90 with inspection cover 25 USI 100 130 Inspection Element...
Страница 37: ...37 NOTES...
Страница 42: ...42 NOTES...
Страница 43: ...43 NOTES...
Страница 44: ...Element4 B V Paxtonstraat 23 8013 RP Zwolle The Netherlands September 2014...