Table 4 (B2, C and correction factors for cable grouping)
B2
E
E
Number of cables
Seated in Cable Duct
Wall fixing or Cable trough
Cable tray
1
1.00
1.00
1.00
2
0.80
0.85
0.87
4
0.65
0.75
0.78
6
0.57
0.72
0.75
9
0.50
0.70
0.73
The total current included for using Table 1 should be the maximum rated current for the machine divided by the
product of the different correction factors. Other correction factors may also be applied ; consult the cable
manufacturers.
Calculation : Example
• The machine has a rated current of 60 A.
• The ambient temperature is 45 °C ; Table 2 gives a correction factor of 0.91.
• Rubber cable insulant : Table 3 gives a correction factor of 0.92.
• The cable is fixed directly to the wall (Column C), with 2 cables side by side. Table 4 gives a correction factor of
0.85.
60 A
Total current :
_________________
= 84 A
0.91 x 0.92 x 0.85
Taking Column C in Table 1 (wall fixing), we obtain a minimum cable section of : 3 x 25 mm².
Содержание WB6-20
Страница 1: ...Installation manual Washer extractors WB6 20 WB6 27 WB6 35 Original instructions 05201148 EN ...
Страница 2: ......
Страница 25: ...Installation manual 25 Back view Right view Drain connection Top view ...
Страница 31: ...Installation manual 31 Important Never handling the machine without the transportation bridles ...
Страница 47: ...Installation manual 47 No Barrier washer Barrier washer ...
Страница 49: ...Installation manual 49 Front view Side view Top view Gas exchanger with draught accelerator ...
Страница 62: ...62 Installation manual ...
Страница 71: ......
Страница 72: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...