3 Note about the A.C. power
According to the EN 60204-1:1997 standard, the machine is provided for A.C. supplies corresponding to the ex-
tracted characteristics below :
4.3.2 A.C. supplies
Voltage:
Steady state voltage: from 0.9 to 1.1 of nominal voltage.
Frequency:
from 0.99 to 1.01 of nominal frequency continuously.
from 0.98 to 1.02 short time.
Harmonics:
Harmonic distortion not to exceed 10 % of the total r.m.s. voltage between live conductors for the sum of the second
through to the fifth harmonic. An additional 2 % of the total r.m.s. voltage between live conductors for the sum of the
sixth through to the 30th harmonic is permissible.
Voltage unbalance:
Neither the voltage of the negative sequence component nor the voltage of the zero sequence component in three-
phase supplies shall exceed 2 % of the positive sequence component.
Voltage interruption:
Supply interrupted or at zero voltage for not more than 3 ms at any random time in the supply cycle. There shall be
more than 1 second between successive interruptions.
Voltage dips:
Voltage dips shall not exceed 20 % of the peak voltage of the supply for more than one cycle. There shall be more
than 1 second between successive dips.
Содержание WB6-20
Страница 1: ...Installation manual Washer extractors WB6 20 WB6 27 WB6 35 Original instructions 05201148 EN ...
Страница 2: ......
Страница 25: ...Installation manual 25 Back view Right view Drain connection Top view ...
Страница 31: ...Installation manual 31 Important Never handling the machine without the transportation bridles ...
Страница 47: ...Installation manual 47 No Barrier washer Barrier washer ...
Страница 49: ...Installation manual 49 Front view Side view Top view Gas exchanger with draught accelerator ...
Страница 62: ...62 Installation manual ...
Страница 71: ......
Страница 72: ...Electrolux Professional AB 341 80 Ljungby Sweden www electroluxprofessional com ...