![Electro Industries Shark 100S Скачать руководство пользователя страница 99](http://html.mh-extra.com/html/electro-industries/shark-100s/shark-100s_installation-and-operation-manual_2379713099.webp)
Doc
#
E145721
6 - 13
6: Ethernet Configuration
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
6.4: Network Module Hardware Initialization
If you don't know your current Network Module settings, or if the settings are lost,
you can use this method to initialize the hardware with known settings you can then
work with.
Main Board
1. Place a shorting block on JP3 and press the Reset button on the main board.
NOTE: JP3 is located on the right hand side, upper corner of the main board. The
shorting block can be "borrowed" from JP2, located at the middle, right hand side.
See the figure shown above.
2. After you press the Reset button, move the jumper back to JP2.
3. Make sure your settings are the same as those in Section 6.2.1. Follow the steps in
Section 6.3 to configure the Network Module.