B: Modbus Map
Doc# E145721 MM-8
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Notes
1
2
3
4
5
6
7
8
9
10
11
12
current FS = CT numerator * CT multi
p
lier
voltage FS = PT numerator * PT multi
p
lier
p
ower FS = CT numerator * CT multi
p
lier * PT numerator * PT multi
p
lier * 3 [ * SQRT(3) for delta hooku
p
]
frequency FS = 60 (or 50)
p
ower factor FS = 1.0
p
ercentage FS = 100.0
angle FS = 180.0
13
14
If the
p
assword is incorrect, a valid res
p
onse is returned but the command is not executed. Use 5555 for the
p
assword if
p
asswords are disabled in the
p
rogrammable settings.
Writing this register causes data to be saved
p
ermanently in EEPROM. If there is an error while saving, a slave device failure exce
p
tion is returned and
p
rogrammable settings mode automatically
terminates via reset.
32-bit IEEE floating
p
oint number s
p
anning 2 registers. The lower-addressed register is the high order half (i.e., contains the ex
p
onent
All registers not ex
p
licitly listed in the table read as 0. Writes to these registers will be acce
p
ted but won't actually change the register (since it doesn't exist).
Meter Data Section items read as 0 until first readings are available or if the meter is not in o
p
erating mode. Writes to these registers will be acce
p
ted but won't actually change the register.
Register valid only in
p
rogrammable settings u
p
date mode. In other modes these registers read as 0 and return an illegal data address exce
p
tion if a write is attem
p
ted.
Not a
pp
licable to Shark 100, V-Switch 1, 2, or 3
M denotes a 1,000,000 multi
p
lier.
Meter command registers always read as 0. They may be written only when the meter is in a suitable mode. The registers return an illegal data address exce
p
tion if a write is attem
p
ted in an incorrect
mode.
Entities to be monitored against limits are identified by Modbus address. Entities occu
p
ying multi
p
le Modbus registers, such as floating
p
oint values, are identified by the lower register address. If any
of the 8 limits is unused, set its identifier to zero. If the indicated Modbus register is not used or is a non-sensical entity for limits, it will behave as an unused limit.
There are 2 set
p
oints
p
er limit, one above and one below the ex
p
ected range of values. LM1 is the "too high" limit, LM2 is "too low". The entity goes "out of limit" on LM1 when its value is greater than
the set
p
oint. It remains "out of limit" until the value dro
p
s below the in threshold. LM2 works similarly, in the o
pp
osite direction. If limits in only one direction are of interest, set the in threshold on the
"wrong" side of the set
p
oint. Limits are s
p
ecified as % of full scale, where full scale is automatically set a
pp
ro
p
riately for the entity being monitored:
Energy registers should be reset after a format change.
Reset commands make no sense if the meter state is LIMP. An illegal function exce
p
tion will be returned.
SINT32 / UINT32
FLOAT
32-bit signed / unsigned integer s
p
anning 2 registers. The lower-addressed register is the high order half
THD not available shows 65535 (=0xFFFF) in all THD and harmonic magnitude registers for the channel when V-switch=4. THD may be unavailable due to low V or I am
p
litude, or delta hooku
p
(V
only).
All 3 voltage angles are measured for Wye and Delta hooku
p
s. For 2.5 Element, Vac is measured and Vab & Vbc are calculated. If a voltage
p
hase is missing, the two voltage angles in which it
p
artici
p
ates are set to zero. A and C
p
hase current angles are measured for all hooku
p
s. B
p
hase current angle is measured for Wye and is zero for other hooku
p
s. If a voltage
p
hase is missing, its
current angle is zero.