5: Communication Installation
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
5: Communication Installation
5.1: Shark® 100S Communication
The Shark® 100S submeter provides two independent communication ports plus a
KYZ pulse output. The first port, Com 1, is an IrDA Port, which uses Modbus ASCII.
The second port, Com 2, provides RS485 or RJ45 Ethernet or WiFi Ethernet
communication (see Chapter 6 for Ethernet communication).
5.1.1: IrDA Port (Com 1)
The Com 1 IrDA port is located on the face of the submeter. The IrDA Port allows the
unit to be set up and programmed with any device capable of IrDA communication,
such as an IrDA-equipped laptop PC or a USB/IrDA wand (such as the USB to IrDA
Adapter [CAB6490] described in Appendix E).
IrDA port settings are
Address: 1
Baud Rate: 57600 Baud
Protocol: Modbus ASCII
Figure 5.1: IrDA Communication