Electro Industries Shark 100S Скачать руководство пользователя страница 20

     

Doc

#    

E145721     

                              

              1 - 6

1: Three Phase Power Measurement

Electro 

Industries/GaugeTech

The Leader In Power Monitoring and Smart Grid Solutions

Electro 

Industries/GaugeTech

The Leader In Power Monitoring and Smart Grid Solutions

1.1.3: Blondell’s Theorem and Three Phase Measurement

In 1893 an engineer and mathematician named Andre E. Blondell set forth the first 
scientific basis for polyphase metering. His theorem states:

If energy is supplied to any system of conductors through N wires, the total power in 
the system is given by the algebraic sum of the readings of N wattmeters so arranged 
that each of the N wires contains one current coil, the corresponding potential coil 
being connected between that wire and some common point. If this common point is 
on one of the N wires, the measurement may be made by the use of N-1 Wattmeters.

The theorem may be stated more simply, in modern language:

In a system of N conductors, N-1 meter elements will measure the power or energy 
taken provided that all the potential coils have a common tie to the conductor in 
which there is no current coil.

Three-phase power measurement is accomplished by measuring the three individual 
phases and adding them together to obtain the total three phase value. In older 
analog meters, this measurement was accomplished using up to three separate ele-
ments. Each element combined the single-phase voltage and current to produce a 
torque on the meter disk. All three elements were arranged around the disk so that 
the disk was subjected to the combined torque of the three elements. As a result the 
disk would turn at a higher speed and register power supplied by each of the three 
wires. 

According to Blondell's Theorem, it was possible to reduce the number of elements 
under certain conditions. For example, a three-phase, three-wire delta system could 
be correctly measured with two elements (two potential coils and two current coils) if 
the potential coils were connected between the three phases with one phase in 
common. 

In a three-phase, four-wire wye system it is necessary to use three elements. Three 
voltage coils are connected between the three phases and the common neutral 
conductor. A current coil is required in each of the three phases.

In modern digital meters, Blondell's Theorem is still applied to obtain proper      
metering. The difference in modern meters is that the digital meter measures each 
phase voltage and current and calculates the single-phase power for each phase. The 
meter then sums the three phase powers to a single three-phase reading.

Содержание Shark 100S

Страница 1: ...S h a r k 100S ...

Страница 2: ...This page intentionally left blank ...

Страница 3: ...es Drive Westbury NY 11590 All rights reserved No part of this publication may be reproduced or transmitted in any form or by any means electronic or mechanical including photocopying record ing or information storage or retrieval systems or any future forms of duplication for any purpose other than the purchaser s use without the expressed written permission of Electro Industries GaugeTech 2011 E...

Страница 4: ...21 ii Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 5: ... replace any product that proves to be defective To exercise this warranty fax or call our customer support department You will receive prompt assistance and return instructions Send the instrument transporta tion prepaid to EIG at 1800 Shames Drive Westbury NY 11590 Repairs will be made and the instrument will be returned This warranty does not apply to defects resulting from unauthorized modific...

Страница 6: ...liability however no responsibility is assumed for inaccuracies The information contained in this document is subject to change without notice This symbol indicates that the operator must refer to an explanation in the operating instructions Please see Chapter 4 for important safety information regarding installation and hookup of the Shark 100S meter FCC Information Regarding the wireless module ...

Страница 7: ...g power monitoring Nexus Series 2001 First auto calibrating meter under glass 2005 Shark 100 Sub meter and Shark 100S wireless sub meter with 802 11 WiFi capability 2007 Shark 200 data logging sub meter with optional I O 2008 First Nexus 1500 transient recorder and power meter with advanced PQ and dual Ethernet communication ports Thirty years since its founding Electro Industries GaugeTech the le...

Страница 8: ...Tech The Leader In Power Monitoring and Smart Grid Solutions Applications Web accessed multifunction power monitoring and control Single and multifunction power monitoring Power quality monitoring Onboard data logging for trending power usage and quality Disturbance analysis Revenue metering and billing Smart grid solutions ...

Страница 9: ...ree Phase Power Measurement 1 1 1 1 Three Phase System Configurations 1 1 1 1 1 Wye Connection 1 1 1 1 2 Delta Connection 1 4 1 1 3 Blondell s Theorem and Three Phase Measurement 1 6 1 2 Power Energy and Demand 1 8 1 3 Reactive Energy and Power Factor 1 12 1 4 Harmonic Distortion 1 14 1 5 Power Quality 1 17 2 Shark 100S Submeter Overview and Specifications 2 1 2 1 Hardware Overview 2 1 2 1 1 Model...

Страница 10: ...ion 4 1 4 1 Considerations When Installing Meters 4 1 4 2 Electrical Connections 4 2 4 3 Ground Connections 4 3 4 4 Voltage Fuses 4 3 4 5 Electrical Connection Diagrams 4 4 5 Communication Installation 5 1 5 1 Shark 100S Communication 5 1 5 1 1 IrDA Port Com 1 5 1 5 1 1 1 USB to IrDA Adapter 5 2 5 1 2 RS485 Communication Com 2 485 Option 5 3 5 1 3 KYZ Output 5 5 5 1 4 Ethernet Connection 5 6 5 2 M...

Страница 11: ...er 6 5 6 3 3 Detailed Configuration Parameters 6 8 6 3 4 Setup Details 6 9 6 3 4 1 Encryption Key 6 11 6 4 Network Module Hardware Initialization 6 13 7 Using the Submeter 7 1 7 1 Introduction 7 1 7 1 A Understanding Submeter Face Elements 7 1 7 1 B Understanding Submeter Face Buttons 7 2 7 2 Using the Front Panel 7 3 7 2 1 Understanding Startup and Default Displays 7 3 7 2 2 Using the Main Menu 7...

Страница 12: ... Hour Accuracy Testing Verification 7 17 7 4 Upgrade the Submeter Using V SwitchTM Key Technology 7 19 A Shark 100S Meter Navigation Maps A 1 A 1 Introduction A 1 A 2 Navigation Maps Sheets 1 to 4 A 1 B Shark 100S Meter Mobus Map A 1 B 1 Introduction B 1 B 2 Modbus Register Map Sections B 1 B 3 Data Formats B 1 B 4 Floating Point Values B 2 B 5 Modbus Register Map B 3 C Shark 100S Meter DNP Map C ...

Страница 13: ...t and Variation D 4 D 4 1 1 Binary Output Status Obj 10 Var 2 D 5 D 4 1 2 Control Relay Output Block Obj 12 Var 1 D 6 D 4 1 3 32 Bit Binary Counter Without Flag Obj 20 Var 5 D 7 D 4 1 4 16 Bit Analog Input Without Flag Obj 30 Var 4 D 7 D 4 1 5 Class 0 Data Obj 60 Var 1 D 13 D 4 1 6 Internal Indications Obj 80 Var 1 D 13 E Using the USB to IrDA Adapter CAB6490 E 1 E 1 Introduction E 1 E 2 Installat...

Страница 14: ...able of Contents Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 15: ...onnections for three phase power a wye connection or a delta connection Each connection has several different manifestations in actual use When attempting to determine the type of connection in use it is a good practice to follow the circuit back to the transformer that is serving the circuit It is often not possible to conclusively determine the correct circuit connection simply by counting the w...

Страница 16: ... 120o electrically Under balanced load conditions the currents are also separated by 120o However unbalanced loads and other conditions can cause the currents to depart from the ideal 120oseparation Three phase voltages and currents are usually represented with a phasor diagram A phasor diagram for the typical connected voltages and currents is shown in Figure 1 2 Figure 1 2 Phasor Diagram Showing...

Страница 17: ...typically tied to the ground or center point of the wye In many industrial applications the facility will be fed with a four wire wye service but only three wires will be run to individual loads The load is then often referred to as a delta connected load but the service to the facility is still a wye service it contains four wires if you trace the circuit back to its source usually a transformer ...

Страница 18: ...oad connections for a delta service Figure 1 3 Three phase Delta Winding Relationship In this example of a delta service three wires will transmit the power to the load In a true delta service the phase to ground voltage will usually not be balanced because the ground is not at the center of the delta Figure 1 4 shows the phasor relationships between voltage and current on a three phase delta circ...

Страница 19: ...common delta connection is the four wire grounded delta used for lighting loads In this connection the center point of one winding is grounded On a 120 240 volt four wire grounded delta service the phase to ground voltage would be 120 volts on two phases and 208 volts on the third phase Figure 1 5 shows the phasor diagram for the voltages in a three phase four wire delta system Figure 1 5 Phasor D...

Страница 20: ...hases and adding them together to obtain the total three phase value In older analog meters this measurement was accomplished using up to three separate ele ments Each element combined the single phase voltage and current to produce a torque on the meter disk All three elements were arranged around the disk so that the disk was subjected to the combined torque of the three elements As a result the...

Страница 21: ...l phase and three phase power values The advantage of simultaneous sampling is the reduction of error introduced due to the difference in time when the samples were taken Figure 1 6 Three Phase Wye Load Illustrating Kirchhoff s Law and Blondell s Theorem Blondell s Theorem is a derivation that results from Kirchhoff s Law Kirchhoff s Law states that the sum of the currents into a node is zero Anot...

Страница 22: ...instantaneous nature of power Energy is always based on some time increment it is the integration of power over a defined time increment Energy is an important value because almost all electric bills are based in part on the amount of energy used Typically electrical energy is measured in units of kilowatt hours kWh A kilowatt hour represents a constant load of one thousand watts one kilowatt for ...

Страница 23: ...er Monitoring and Smart Grid Solutions specified that the load is constant over that minute we can convert the power reading to an equivalent consumed energy reading by multiplying the power reading times 1 60 converting the time base from minutes to hours Figure 1 7 Power Use over Time 0 10 20 30 40 50 60 70 80 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 Time minutes s t t a w o l i k ...

Страница 24: ...ry to accumulate the energy readings as illustrated in Figure 1 7 and adjust the energy reading to an hourly value that constitutes the demand In the example the accumulated energy is 14 92 kWh But this measurement was made over a 15 minute interval To convert the reading to a demand value it must be normalized to a 60 minute interval If the pattern were repeated for an additional three 15 minute ...

Страница 25: ...each interval typically falls between 50 and 70 kWh However during two intervals the energy rises sharply and peaks at 100 kWh in interval number 7 This peak of usage will result in setting a high demand reading For each interval shown the demand value would be four times the indicated energy reading So interval 1 would have an associated demand of 240 kWh hr Interval 7 will have a demand value of...

Страница 26: ...onent of power that is the combination of the voltage and the value of corresponding current that is directly in phase with the voltage However in actual practice the total current is almost never in phase with the voltage Since the current is not in phase with the voltage it is necessary to consider both the inphase component and the component that is at quadrature angularly rotated 90o or perpen...

Страница 27: ...ied value A common method of measuring reactive power requirements is power factor Power factor can be defined in two different ways The more common method of calculating power factor is the ratio of the real power to the apparent power This relationship is expressed in the following formula Total PF real power apparent power watts VA This formula calculates a power factor quantity known as Total ...

Страница 28: ...1 4 Harmonic Distortion Harmonic distortion is primarily the result of high concentrations of non linear loads Devices such as computer power supplies variable speed drives and fluorescent light ballasts make current demands that do not match the sinusoidal waveform of AC electricity As a result the current waveform feeding these loads is periodic but not sinusoidal Figure 1 10 shows a normal sinu...

Страница 29: ...requencies that are multiples of the fundamental 60 Hz frequency This modeling is performed by mathematically disassembling the distorted waveform into a collection of higher frequency waveforms These higher frequency waveforms are referred to as harmonics Figure 1 12 shows the content of the harmonic frequencies that make up the distortion portion of the waveform in Figure 1 11 Figure 1 12 Wavefo...

Страница 30: ...ch as the 3rd 5th 7th and 9th However newer new linear loads are introducing significant quantities of higher order harmonics Since much voltage monitoring and almost all current monitoring is performed using instrument transformers the higher order harmonics are often not visible Instrument transformers are designed to pass 60 Hz quantities with high accuracy These devices when designed for accur...

Страница 31: ...ould not be confused with waveform recording that is used to record multiple cycles of all voltage and current waveforms in response to a transient condition 1 5 Power Quality Power quality can mean several different things The terms power quality and power quality problem have been applied to all types of conditions A simple definition of power quality problem is any voltage current or frequency ...

Страница 32: ... quality professional for assistance in defining the cause and possible solutions to the problem Cause Disturbance Type Source Impulse transient Transient voltage disturbance sub cycle duration Lightning Electrostatic discharge Load switching Capacitor switching Oscillatory transient with decay Transient voltage sub cycle duration Line cable switching Capacitor switching Load switching Sag swell R...

Страница 33: ...t that can be read and configured with an IrDA equipped device such as a laptop PC The unit is designed with advanced measurement capabilities allowing it to achieve high performance accuracy The Shark 100S meter is specified as a 0 2 class energy meter for billing applications To verify the submeter s performance and calibration power providers use field test standards to verify that the unit s e...

Страница 34: ...perception Modbus RTU over Serial and Modbus TCP over Ethernet Serial RS485 communication Ethernet and wireless Ethernet WiFi Easy to use faceplate programming IrDA port for laptop PC remote read Direct interface with most Building Management systems The Shark 100S submeter uses standard 5 or 1 Amp CTs either split or donut It surface mounts to any wall and is easily programmed The unit is designe...

Страница 35: ... technology is a virtual firmware based switch that allows you to enable meter features through communication This allows the unit to be upgraded after installation to a higher model without removing it from service Available V SwitchTM Keys V SwitchTM 3 V 3 Volts Amps kW kVAR PF kVA Freq kWh kVAh kVARh DNP 3 0 V SwitchTM 4 V 4 Volts Amps kW kVAR PF kVA Freq kWh kVAh kVARh THD Monitoring Limit Exc...

Страница 36: ...nd some additionally as average maximum and minimum values The Shark 100S meter measures harmonics up to the 7th order for Current and up to the 3rd order for Voltage Shark 100S Meter Measured Values Measured Values Real Time Average Maximum Minimum Voltage L N X X X Voltage L L X X X Current per Phase X X X X Current Neutral X Watts X X X X VAR X X X X VA X X X X PF X X X X Watt hr X Watt hr X Wa...

Страница 37: ...3 subintervals and providing a new Demand reading every 5 minutes based on the last 15 minutes Utility Demand features can be used to calculate kW kVAR kVA and PF readings All other parameters offer Max and Min capability over the user selectable averaging period Voltage provides an Instantaneous Max and Min reading which displays the highest surge and lowest sag seen by the meter 2 2 Specificatio...

Страница 38: ...ale to any PT Ratio Current Inputs Class 10 5A Nominal 10 Amp Maximum Class 2 1A Nominal 2 Amp Secondary Burden 0 005VA Per Phase Max at 11 Amps Pickup Current 0 1 of Nominal Connections Screw terminal 6 32 screws Diagram 4 1 Current Surge Withstand 100A 10 seconds at 23o C Reading Programmable Full Scale to any CT Ratio Isolation All Inputs and Outputs are galvanically isolated and tested to 2500...

Страница 39: ...ic THD of Total Harmonic Distortion A D Conversion 6 Simultaneous 24 bit Analog to Digital Converters Update Rate Watts VAR and VA Every 6 cycles e g 100 milliseconds Ten times per second 60Hz All other parameters Every 60 cycles e g 1 second 60Hz Communication Format 1 RS485 2 IrDA Port through Face Plate Protocols Modbus RTU Modbus ASCII DNP 3 0 Modbus TCP for Ethernet enabled Com Port Baud Rate...

Страница 40: ...eight 4 pounds KYZ RS485 Port Specifications RS485 Transceiver meets or exceeds EIA TIA 485 Standard Type Two wire half duplex Min Input Impedance 96kΩ Max Output Current 60mA Wh Pulse KYZ output contacts and infrared LED light pulses through face plate see Section 7 4 for Kh values Pulse Width 40ms Full Scale Frequency 6Hz Contact type Solid State SPDT NO C NC Relay type Solid state Peak switchin...

Страница 41: ...mart Grid Solutions Infrared LED Peak Spectral Wavelength 940nm Reset State Off Internal Schematic Output Timing De energized state NC C NO NC C NO NO C NC NO C NC NO C NC NC C NO 40ms 40ms 3600 Watt P pulse Watthour Kh s T º ª LED ON LED ON LED OFF LED OFF LED OFF IR LED Light Pulses Through face plate KYZ output Contact States Through Backplate P Watt Not a scaled value Kh See Section 7 4 for va...

Страница 42: ... 50 or 60 Hz as per order 5A Class 10 nominal unit Parameter Accuracy Accuracy Input Range Voltage L N V 0 1 of reading2 69 to 480 V Voltage L L V 0 1 of reading 120 to 600 V Current Phase A 0 1 of reading1 0 15 to 5 A Current Neutral calculated A 2 0 of Full Scale1 0 15 to 5 A 45 to 65 Hz Active Power Total W 0 2 of reading1 2 0 15 to 5 A 69 to 480 V 0 5 to 1 lag lead PF Active Energy Total Wh 0 ...

Страница 43: ...r 1A Class 2 Nominal the input current range for Accuracy specification is 20 of the values listed in the table 2 For unbalanced voltage inputs where at least one crosses the 150V auto scale threshold for example 120V 120V 208V system degrade accuracy by additional 0 4 Apparent Energy Total VAh 0 2 of reading1 2 0 15 to 5 A 69 to 480 V 0 5 to 1 lag lead PF Power Factor 0 2 of reading1 2 0 15 to 5 ...

Страница 44: ...rview and Specifications Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 45: ...ee Chapter 4 for wiring diagrams Mount the meter in a dry location which is free from dirt and corrosive substances Recommended Tools for Shark 100S Installation 2 Phillips screwdriver Wire cutters 3 2 Install the Base 1 Determine where you want to install the submeter 2 With the submeter power off open the top of the submeter Use the front cover support to keep the cover open as you perform the i...

Страница 46: ...er support if you are able to open the front cover to the extent that you can fit the front cover support into its base DO NOT rest the front cover support on the inside of the meter even for a short time by doing so you may damage components on the board assembly 3 Find the 4 Installation Slots and insert screws through each slot into the wall or panel 4 Fasten securely DO NOT overtighten 3 2 1 M...

Страница 47: ...llation Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Figure 3 3 Front Dimensions v CM v CM NTENNA ENGTH v CM ...

Страница 48: ...rdware Installation Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Figure 3 4 Side Dimensions v CM ...

Страница 49: ...Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Figure 3 5 Open Cover Dimensions Figure 3 6 Bottom View with Access Holes 12 30 4cm w DN ...

Страница 50: ...3 6 CAUTION To avoid damaging components on the board assembly make sure the front cover support is in the upright position before closing the front cover 2 Using the 3 enclosed screws secure the cover to the base in three places DO NOT overtighten you may damage the cover 3 The unit can be sealed after the front cover is closed To seal the unit thread the seal tag through the housing located betw...

Страница 51: ...tputs and their circuits All Primary and Secondary circuits can at times produce lethal voltages and currents Avoid contact with any current carrying surfaces Do not use the meter or any I O Output Device for primary protection or in an energy limiting capacity The meter can only be used as secondary pro tection Do not use the meter for applications where failure of the meter may cause harm or dea...

Страница 52: ...PERFORMED BY THE FACTORY DISCONNECT DEVICE The following part is considered the equip ment disconnect device A SWITCH OR CIRCUIT BREAKER SHALL BE INCLUDED IN THE END USE EQUIPMENT OR BUILDING INSTALLA TION THE SWITCH SHALL BE IN CLOSE PROXIMITY TO THE EQUIP MENT AND WITHIN EASY REACH OF THE OPERATOR THE SWITCH SHALL BE MARKED AS THE DISCONNECTING DEVICE FOR THE EQUIPMENT 4 2 Electrical Connections...

Страница 53: ...round 4 4 Voltage Fuses EIG recommends the use of fuses on each of the sense voltages and on the control power even though the wiring diagrams in this chapter do not show them Use a 0 1 Amp fuse on each Voltage input Use a 3 Amp fuse on the power supply Electronic Circuits Ethernet RJ45 Jack Ia Ia Ib Ib Ic Ic Z K Y SH Va Vb Vc Vn L1 L2 PE RS 485 KYZ Pulse Output Wireless Ethernet Connection RS485 ...

Страница 54: ...h Direct Voltage 3 Element a Dual Phase Hookup b Single Phase Hookup 3 Three Phase Four Wire System Wye with Direct Voltage 2 5 Element 4 Three Phase Four Wire Wye with PTs 3 Element 5 Three Phase Four Wire Wye with PTs 2 5 Element 6 Three Phase Three Wire Delta with Direct Voltage No PTs 2 CTs 7 Three Phase Three Wire Delta with Direct Voltage No PTs 3 CTs 8 Three Phase Three Wire Delta with 2 PT...

Страница 55: ...d Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 1 Service WYE 4 Wire with No PTs 3 CTs Select 3 EL WYE 3 Element Wye in Meter Programming setup Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C N A B C N Ia Ib Ic Power Supply Inputs L2 is for Neutral ...

Страница 56: ...ch The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 1a Dual Phase Hookup Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C N A B C N Ia Ib Ic Power Supply Inputs ...

Страница 57: ...h The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 1b Single Phase Hookup Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C N A B C N Ia Ib Ic Power Supply Inputs ...

Страница 58: ...id Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 2 Service 2 5 Element WYE 4 Wire with No PTs 3 CTs Select 2 5 EL WYE 2 5 Element Wye in Meter Programming setup Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C N A B C N Ia Ib Ic Power Supply Inputs ...

Страница 59: ...d Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 3 Service WYE 4 Wire with 3 PTs 3 CTs Select 3 EL WYE 3 Element Wye in Meter Programming setup Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vn L1 L2 PE A B C N A B C N Ia Ib Ic Power Supply Inputs ...

Страница 60: ...nd Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 4 Service 2 5 Element WYE 4 Wire with 2 PTs 3 CTs Select 2 5 EL WYE 2 5 Element Wye in Meter Programming setup Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C N A B C N Ia Ib Ic Power Supply Inputs ...

Страница 61: ... and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 5 Service Delta 3 Wire with No PTs 2 CTs Select 2 Ct dEL 2 CT Delta in Meter Programming setup Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C A B C Ia Ic Power Supply Inputs ...

Страница 62: ...nd Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 6 Service Delta 3 Wire with No PTs 3 CTs Select 2 Ct dEL 2 CT Delta in Meter Programming setup Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C A B C Ia Ic Ib Power Supply Inputs ...

Страница 63: ... and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 7 Service Delta 3 Wire with 2 PTs 2 CTs Select 2 Ct dEL 2 CT Delta in Meter Programming setup Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C A B C Ia Ic Electronic Circuits Power Supply Inputs ...

Страница 64: ...and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 8 Service Delta 3 Wire with 2 PTs 3 CTs Select 2 Ct dEL 2 CT Delta in Meter Programming setup Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C A B C Ic Electronic Circuits Ib Ia Power Supply Inputs ...

Страница 65: ...rent Only Measurement Three Phase Select 3 EL WYE 3 Element Wye in Meter Programming setup NOTE Even if the meter is used for only Amp readings the unit requires a Volts AN reference Please make sure that the Voltage input is attached to the meter AC Control Power can be used to provide the reference signal Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B C N A B C N Ia Ib Ic 20VAC...

Страница 66: ... Current Only Measurement Dual Phase Select 3 EL WYE 3 Element Wye in Meter Programming setup NOTE Even if the meter is used for only Amp readings the unit requires a Volts AN reference Please make sure that the Voltage input is attached to the meter AC Control Power can be used to provide the reference signal Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A B N A B N Ia Ib 20VAC Min...

Страница 67: ...ice Current Only Measurement Single Phase Select 3 EL WYE 3 Element Wye in Meter Programming setup NOTE Even if the meter is used for only Amp readings the unit requires a Volts AN reference Please make sure that the Voltage input is attached to the meter AC Control Power can be used to provide the reference signal Electronic Circuits Ia Ia Ib Ib Ic Ic Va Vb Vc Vref L1 L2 PE A N A N Ia 20VAC Minim...

Страница 68: ...trical Installation Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 69: ... Com 1 is an IrDA Port which uses Modbus ASCII The second port Com 2 provides RS485 or RJ45 Ethernet or WiFi Ethernet communication see Chapter 6 for Ethernet communication 5 1 1 IrDA Port Com 1 The Com 1 IrDA port is located on the face of the submeter The IrDA Port allows the unit to be set up and programmed with any device capable of IrDA communication such as an IrDA equipped laptop PC or a US...

Страница 70: ...ance is 0 to 3 meters approximately 1 foot The USB to IrDA Adapter enables wireless data transfer between a PC and the submeter The adapter can also be used with other IrDA compatible devices The adapter is fully compatible with IrDA 1 1 and USB 1 1 specifications System Requirements IBM PC Pentium based computer 2 Gigabytes of RAM preferable Available USB port CD ROM drive Windows 98 Windows XP o...

Страница 71: ...nt of the meter under the cover A connection can easily be made to a Master device or to other slave devices as shown below NOTE Care should be taken to connect to and to connections The Shark 100S submeter s RS485 connection can be programmed with the buttons on the face of the meter or by using Communicator EXT software Standard RS485 Port Settings Address 001 to 247 Baud Rate 9600 19200 38400 o...

Страница 72: ...toring and Smart Grid Solutions Protocol Modbus RTU Modbus ASCII or DNP 3 0 The position of Jumper 2 JP2 must be set for either RS485 or Ethernet communi cation See the figure below You put the jumper on positions 2 and 3 for LAN Ether net communication and on 1 and 2 for RS485 communication 4 1 3 1 3 1 8 7 8 7 8 7 WD s e i r t s u d n I o r t c e l E h c e T e g u a G 0 23 3ETTINGS ...

Страница 73: ...The KYZ pulse output provides pulsing energy values that verify the submeter s readings and accuracy The KYZ Pulse Output is located on the face of the meter under the cover and just below the RS485 connection See Section 2 2 for the KYZ output specifications see Section 7 3 1 for pulse constants Electronic Circuits Ia Ia Ib Ib Ic Ic Z K Y SH Va Vb Vc Vn L1 L2 PE RS 485 Pulse Contacts Wireless Eth...

Страница 74: ...s 2 3 You can use either wired Ethernet or WiFi For wired Ethernet use Standard RJ45 10 100BaseT cable to connect to the Shark 100S submeter The RJ45 line is inserted into the RJ45 port of the meter For Wi Fi connections make sure you have the correct antenna attached to the meter Refer to Chapter 6 for instructions on how to set up the Network Module See the JP2 figure and instructions on page 5 ...

Страница 75: ...to program the meter and communicate to other devices Meter Connection To provide power to the meter use one of the wiring diagrams in Chapter 4 or attach an Aux cable to GND L and N The RS485 cable attaches to SH and as shown in Section 5 1 2 5 2 1 How to Connect to the Submeter 1 Open Communicator EXT software 2 Click the Connect icon on the Icon bar The Connect screen opens showing the Initial ...

Страница 76: ...Solutions meter via Serial Port or Network Use the pull down menus to make any necessary changes 3 Click the Connect button on the screen NOTE You may have to disconnect power reconnect power and then click Connect The Device Status screen appears confirming a connection 4 Click OK 5 The Communicator EXT Main screen appears Click the Profile icon in the Title Bar Serial Port Connection Network Con...

Страница 77: ...art Grid Solutions 6 You will see the Shark 100S meter s Device Profile screen The tabs at the top of the screen allow you to navigate between settings screens see below 7 Click the Communications tab You will see the following screen Use this screen to enter communication settings for the meter s two on board ports the IrDA port COM 1 and RS485 port COM 2 Make any necessary changes to settings ...

Страница 78: ...odbus ASCII or DNP Baud Rate 9600 to 57600 Response Delay 0 750 msec DNP Options for Voltage Current and Power these fields allow you to choose Primary or Secondary Units for DNP and to set custom scaling if you choose Primary See Chapter 5 in the Communicator EXT User Manual for more information 9 When changes are complete click the Update Device button to send the new profile to the meter 10 Cli...

Страница 79: ...Refer to Chapter 5 in the Communicator EXT User Manual for detailed instructions on configuring all settings of the meter s Device Profile You can view the manual online by clicking Help Contents from the Communicator EXT Main screen CT PT Ratios and System Hookup The screen fields and acceptable entries are as follows CT Ratios CT Numerator Primary 1 9999 CT Denominator Secondary 5 or 1 Amp NOTE ...

Страница 80: ...hases Displayed A AB or ABC NOTE Voltage Full Scale PT Numerator x PT Multiplier Example A 14400 120 PT would be entered as PT Numerator 1440 PT Denominator 120 Multiplier 10 This example would display a 14 40kV Example CT Settings 200 5 Amps Set the Ct n value for 200 Ct Multiplier value for 1 800 5 Amps Set the Ct n value for 800 Ct Multiplier value for 1 2 000 5 Amps Set the Ct n value for 2000...

Страница 81: ...Pt n value is 3450 Pt d value is 115 Pt Multiplier value is 100 345 000 69 Volts Pt n value is 345 Pt d value is 69 Pt Multiplier value is 1000 NOTE Settings are the same for Wye and Delta configurations Energy and Display The settings on this screen determine the display configuration of the meter s faceplate The screen fields and acceptable entries are as follows Power and Energy Format Power Sc...

Страница 82: ...r Direction View as Load or View as Generator Demand Averaging Averaging Method Block or Rolling Interval Minutes 5 15 30 or 60 Sub Interval if Rolling is selected 1 4 Auto Scroll Click to set On or Off Display Configuration Click Values to be displayed NOTE You MUST select at least ONE NOTE If incorrect values are entered on this screen the following message appears WARNING Current CT PT and Ener...

Страница 83: ...g and Smart Grid Solutions Settings The screen fields are as follows Password NOTE The meter is shipped with Password Disabled There is NO DEFAULT PASSWORD Enable Password for Reset click to Enable Enable Password for Configuration click to Enable Change Password click to Change Change VSwitch click to Change see Section 7 4 for instructions Device Designation optional user assigned label ...

Страница 84: ...it an out of limit condition occurs Once they are configured you can view the out of Limits or Alarm conditions in the Limits Log or Limits Polling screen You can also use Limits to trigger relays See the Communicator EXT User Manual for details For up to 8 Limits set Address Modbus Address 1 based Label Your designation for the limit High Set Point of Full Scale Example 100 of 120VFS 120V 90 of 1...

Страница 85: ...is Point to go back in Limit Your settings appear in the Table at the bottom of the screen NOTES If Return Hysteresis is High Set Point the Limit is Disabled IMPORTANT When you have finished making changes to the Device Profile click Update Device to send the new Profile settings to the meter NOTE Refer to Chapter 5 of the Communicator EXT User s Manual for additional instructions on configuring t...

Страница 86: ...nication Installation Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 87: ...eter does not need to be directly connected wired to these comput ers for it to be accessed This chapter outlines the procedures you use to set up the Shark 100S submeter to function via its Ethernet configuration IMPORTANT These instructions are for Shark 100S meters that have a Reset button located on the main board You can easily tell whether or not your meter has a Reset button open the front ...

Страница 88: ...y are the settings programmed into your meter when it is shipped to you You may need to modify some of these settings when you set up your Ethernet configuration NOTES Change Settings 1 and 6 ONLY Settings 2 3 and 4 must be the same as shown in Section 6 2 1 If they are not reset them to the values shown in Section 6 2 1 If setting 3 is not CP0 Defaults In the procedure for Network Module Hardware...

Страница 89: ...Protocol Modbus RTU Slave s attached Serial Interface 57600 8 N 1 RS232 CH1 3 Modem Configurable Pin Settings CP0 Defaults In CP1 GPIO In CP2 GPIO In CP3 GPIO In CP4 GPIO In CP5 GPIO In CP6 GPIO In CP7 GPIO In CP8 GPIO In CP9 GPIO In CP10 GPIO In RTS Output Fixed High Active 4 Advanced Modbus Protocol settings Slave Addr Unit Id Source Modbus TCP header Modbus Serial Broadcasts Disabled Id 0 auto ...

Страница 90: ... consult your Network Administrator before performing these procedures since some functions may be restricted to the Network Administrator If you have only one Ethernet adapter network card the screen displays only that configuration You will use this Ethernet adapter to access the Shark 100S meter s Network Module You may have to configure the Ethernet adapter in order to use it with the Shark 10...

Страница 91: ...rid Solutions 6 3 2 Configuring the Ethernet Adapter 1 From the PC s Start Menu select Settings Network Connections or Control Panel Network Connections You will see a screen like the one shown below 2 Right click on the Local Area Network connection you will be using to connect to the Shark 100S submeter and select Properties from the pull down menu You will see the screen shown on the next page ...

Страница 92: ...ader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 3 Select Internet Protocol TCP IP from the middle of the screen and click the Properties button You will see the screen shown on the next page ...

Страница 93: ...In Power Monitoring and Smart Grid Solutions 4 Click the Use the Following IP Address radio button The screen changes to allow you to enter the IP Address and Subnet Mask a Enter 10 0 0 2 in the IP Address field b Enter 255 255 255 0 in the Subnet Mask field 3 Click the OK button 4 You can now close the Local Area Connection Properties and Network Connection windows ...

Страница 94: ...nu click Run and type cmd 2 Click the OK button to bring up Windows s Command Prompt window 3 In the Command Prompt window type telnet 10 0 0 1 9999 and press the Enter key NOTE Be sure to include a space between the IP address and 9999 The following parameters appear for example 4 Press Enter again quickly 5 After entering Setup Mode confirm by pressing Enter you can configure the parameters for ...

Страница 95: ... they are not reset them to the values shown in Section 6 2 1 Network IP Settings Detail 1 Set device with static IP Address Network Mode 0 Wired only 1 Wireless Only 0 1 IP Address 010 192 000 168 000 000 001 Set Gateway IP Address N Y Gateway IP Address 192 168 000 001 Set Netmask N for default Y Y 255 255 255 000 Change telnet config password N N Serial Mode Settings 2 Make sure these settings ...

Страница 96: ...e Space bar until the following appears on the screen CP0 Function hit space to toggle Defaults In Press Enter The following appears on the screen Invert active low Y Press Y Ignore other settings press Enter through the rest of Setting 3 Advanced Modbus Protocol settings 4 Make sure these settings match those shown in Section 6 2 1 Slave address 0 for auto or 1 255 fixed otherwise 0 0 Allow Modbu...

Страница 97: ...NTICAL to the settings for LWAN shown above For programming see the User s Manual for the Wireless Access Point in use See Section 6 3 4 1 for information on using an Encryption key Exiting the screen CAUTION DO NOT PRESS D Press S to Save the settings you ve entered 6 3 4 1 Encryption Key EIG recommends that you use 128 bit encryption when setting up your Ethernet configuration In the WLAN Settin...

Страница 98: ...ssphrase 2 Click the Generate Keys button Your Hexadecimal WEP Keys appear 3 Input the 128 bit Key in the Change Key section of the WLAN Settings 6 4 Continue inputting settings 5 Press S to Save your settings PASSPHRASE TO HEXADECIMAL WEP KEYS Enter the passphrase below 1009egbck001036ab Generate keys PASSPHRASE TO HEXADECIMAL WEP KEYS The passphrase 1009egbcke001306ab produces the following keys...

Страница 99: ...known settings you can then work with Main Board 1 Place a shorting block on JP3 and press the Reset button on the main board NOTE JP3 is located on the right hand side upper corner of the main board The shorting block can be borrowed from JP2 located at the middle right hand side See the figure shown above 2 After you press the Reset button move the jumper back to JP2 3 Make sure your settings ar...

Страница 100: ...ernet Configuration Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 101: ...Navigation maps 7 1 A Understanding Submeter Face Elements Figure 7 1 Faceplate with Elements The meter face features the following elements Reading Type Indicator e g Max Parameter Designator e g Volts L N Watt Hour Test Pulse Energy pulse output to test accuracy Scaling Factor Kilo or Mega multiplier of displayed readings of Load Bar Graphic Display of Amps as of the Load Refer to Section 7 3 fo...

Страница 102: ... 7 2 Faceplate with Buttons The meter face has Menu Enter Down and Right buttons which let you perform the following functions View Meter Information Enter Display Modes Configure Parameters may be Password Protected Perform Resets may be Password Protected Perform LED Checks Change Settings View Parameter Values Scroll Parameter Values View Limit States V 4 0000 A B C MENU ENTER MAX MIN LM1 LM2 T...

Страница 103: ...igate through each mode and its related screens NOTES See Appendix A for the complete display mode Navigation maps The meter can also be configured using software see Chapter 5 and the Communi cator EXT User Manual for instructions 7 2 1 Understanding Startup and Default Displays Upon Power Up the meter displays a sequence of screens Lamp Test screen where all LEDs are lit Lamp Test screen where a...

Страница 104: ...ess the Menu button The Main Menu screen appears The Reset Demand mode rStd appears in the A window Use the Down button to scroll causing the Reset Energy rStE Configuration CFG Operating OPr and Information InFo modes to move to the A window The mode that is currently flashing in the A window is the Active mode which means it is the mode that can be configured For example Press Down Twice CFG mov...

Страница 105: ...t Energy No screen appears If you press the Enter button again the Main Menu appears with the next mode in the A window The Down button does not affect this screen If you press the Right button the Reset Demand YES or Reset Energy YES screen appears Press Enter to perform a reset NOTE If Password protection is enabled for reset you must enter the four digit password before you can reset the meter ...

Страница 106: ...en the correct number appears for that dash use the Right button to move to the next dash Example The left screen below shows four dashes The right screen shows the dis play after the first two digits of the password have been entered 2 When all 4 digits of the password have been selected press the Enter button If you are in Reset Mode and you enter the correct password rSt dMd donE or rSt EnEr do...

Страница 107: ...eters screen appears 4 Press the Down button to scroll through the configuration parameters Scroll SCrL CT PT Connection Cnct and Port The parameter currently Active i e configurable flashes in the A window 5 Press the Enter button to access the Setting screen for the currently active parameter NOTE You can use the Enter button to scroll through all of the Configuration param eters and their Setti...

Страница 108: ...rd screen appears See Section 7 2 4 for instruc tions on entering a password 7 Once you have entered the new setting press the Menu button twice 8 The Store ALL YES screen appears You can either Press the Enter button to save the new setting Press the Right button to access the Store ALL no screen then press the Enter button to cancel the Save 9 If you have saved the settings the Store ALL done sc...

Страница 109: ... SwitchTM key Refer to Section 7 4 for informa tion on V SwitchTM keys To enable or disable Auto scrolling 1 Press the Enter button when SCrl is in the A window The Scroll YES screen appears 2 Press either the Right or Down button if you want to access the Scroll no screen To return to the Scroll YES screen press either button 3 Press the Enter button on either the Scroll YES screen to enable auto...

Страница 110: ...t d screen is preset to a 5 amp or 1 amp value at the factory and cannot be changed a To change the value for the CT numerator From the Ct n screen Use the Down button to select the number value for a digit Use the Right button to move to the next digit b To change the value for CT scaling From the Ct S screen Use the Right button or the Down button to choose the scaling you want The Ct S setting ...

Страница 111: ...tons to set Ct n Ct d cannot be changed Use buttons to select scaling 7 2 5 3 Configuring PT Setting The PT Setting has three parts Pt n numerator Pt d denominator and Pt S scal ing 1 Press the Enter button when Pt is in the A window The PT n screen appears You can either Change the value for the PT numerator Access one of the other PT screens by pressing the Enter button press Enter once to acces...

Страница 112: ...setting is entered press the Menu button twice 3 The STOR ALL YES screen appears Press Enter to save the new PT setting Example PT Settings 277 277 Volts Pt n value is 277 Pt d value is 277 Pt S value is 1 14 400 120 Volts Pt n value is 1440 Pt d value is 120 Pt S value is 10 138 000 69 Volts Pt n value is 1380 Pt d value is 69 Pt S value is 100 345 000 115 Volts Pt n value is 3450 Pt d value is 1...

Страница 113: ...password refer to Section 7 2 4 for instruc tions on doing so 3 When you have made your selection press the Menu button twice 4 The STOR ALL YES screen appears Press Enter to save the setting Use buttons to select configuration 7 2 5 5 Configuring Communication Port Setting Port configuration consists of Address a three digit number Baud Rate 9600 19200 38400 or 57600 and Protocol DNP 3 0 Modbus R...

Страница 114: ...the bAUd screen Use the Right button or the Down button to select the setting you want c To select the Protocol From the Prot screen Press the Right button or the Down button to select the setting you want NOTE If you are prompted to enter a password refer to Section 7 2 4 for instruc tions on doing so 2 When you have finished making your selections press the Menu button twice 3 The STOR ALL YES s...

Страница 115: ...rrently Active i e displayed parameter has the Indicator light next to it on the right face of the meter 2 Press the Right button to view additional readings for that parameter The table below shows possible readings for Operating mode Sheet 2 in Appendix A shows the Operating mode Navigation map NOTE Readings or groups of readings are skipped if not applicable to the meter type or hookup or if th...

Страница 116: ...the Shark 100S meter s front panel provides a graphic representation of Amps The segments light according to the load as shown in the table below When the Load is over 120 of Full Load all segments flash On 1 5 secs and Off 0 5 secs Segments Load Full Load none no load 1 1 1 2 15 1 3 30 1 4 45 1 5 60 1 6 72 1 7 84 1 8 96 1 9 108 1 10 120 All Blink 120 0000 A B C MENU ENTER MAX MIN LM1 LM2 THD PRG ...

Страница 117: ...and calibration power providers use field test standards to ensure that the unit s energy measurements are correct Since the Shark 100S submeter is a traceable revenue meter it contains a utility grade test pulse that can be used to gate an accuracy standard This is an essential feature required of all billing grade meters Refer to Figure 7 5 for an example of how this process works Refer to Table...

Страница 118: ...Constants for Accuracy Testing Kh Watt hour per pulse NOTES Minimum pulse width is 40 milliseconds Refer to Chapter 2 Section 2 2 for Wh Pulse specifications Input Voltage Level Class 10 Models Class 2 Models Below 150V 0 2505759630 0 0501151926 Above 150V 1 0023038521 0 2004607704 A B C MENU ENTER MAX MIN LM1 LM2 THD PRG VOLTS L N VOLTS L L AMPS WNARP VA Hz lrDA Wh VARh VAh 120 90 60 30 LOAD MEGA...

Страница 119: ...key 4 V 4 Volts Amps kW kVAR PF kVA Freq kWh kVAh kVARh THD Monitoring Limit Exceeded Alarms DNP 3 0 To obtain a V SwitchTM key V SwitchTM keys are based on the particular serial number of the ordered submeter To obtain a higher V SwitchTM key you need to provide EIG with the following informa tion Serial number s of the submeter s you want to upgrade Desired V SwitchTM key upgrade Credit Card or ...

Страница 120: ... Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 5 Enter the Upgrade code provided by EIG 6 Click OK The V SwitchTM key is changed and the submeter resets NOTE For more details on software configuration refer to the Communicator EXT User Manual ...

Страница 121: ...nd instructions for programming the meter using them The meter can also be programmed using software see Chapter 5 and the Communicator EXT User Manual A 2 Navigation Maps Sheets 1 to 4 The Shark 100S meter s Navigation maps begin on the next page The maps show in detail how to move from one screen to another and from one display mode to another using the buttons on the face of the meter All displ...

Страница 122: ...T MODE sequence of screens to get password if required and reset meter data See sheet 3 single screen all screens for a display mode button group of screens MENU ENTER DOWN RIGHT Navigation Editing Returns to previous menu from any screen in any mode Indicates acceptance of the current screen and advances to the next one Navigation and edit buttons No digits or legends are blinking On a menu down ...

Страница 123: ...is skipped if not applicable to the meter type or hookup or if explicitly disabled via programmable settings 2 DOWN occurs without user intervention every 7 seconds if scrolling is enabled 3 No Volts_LN screens for Delta 2 CT hookup 4 Scrolling is suspended for 3 minutes after any button press 5 AMPS_NEUTRAL appears for WYE hookups RIGHT RIGHT RIGHT RIGHT RIGHT DOWN2 from any VOLTS_LN screen DOWN2...

Страница 124: ...et 3 RESET_NO RST ALL no blinking is password required RIGHT RIGHT ENTER yes is password correct ENTER 2 sec no RIGHT DOWN RESET_YES RST ALL yes blinking reset all max min values RESET_CONFIRM RST ALL DONE RESET_ENTER_PW PASS one blinking make next digit blink increment blinking digit yes from MAIN MENU MENU from any reset mode screen RESET_PW_FAIL PASS FAIL no ENTER 2 sec to previous operating mo...

Страница 125: ...R ALL yes blinking no yes save new configuration MENU SAVE_CONFIRM STOR ALL DONE 2 sec reboot ENTER ENTER CT_MULT_EDIT CT S 1 or 10 or 100 choice blinking if edit CTN_EDIT CT N one blinking if edit ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER ENTER DOWN RIGHT DOWN RIGHT DOWN or RIGHT DOWN or RIGHT RIGHT DOWN or RIGHT3 ENTER DOWN or RIGHT DOWN or RIGHT RIGHT DOWN or RIGHT ENTER2 ENTE...

Страница 126: ... S Meter Navigation Maps Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 127: ...ections Fixed Data Section Registers 1 47 details the Meter s Fixed Information described in Section 8 2 Meter Data Section Registers 1000 5003 details the Meter s Readings including Primary Readings Energy Block Demand Block Maximum and Minimum Blocks THD Block Phase Angle Block and Status Block Operating Mode readings are described in Section 7 2 6 Commands Section Registers 20000 26011 details ...

Страница 128: ...010001110110111001 1 x 210 x 1 75871956 1800 929 Formula Explanation C4E11DB9 hex 11000100 11100001 00011101 10111001 binary The sign of the mantissa and therefore the number is 1 which represents a nega tive value The Exponent is 10001001 binary or 137 decimal Register 0 1 Byte 0 1 0 1 Bit 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 7 6 5 4 3 2 1 0 Meaning s e e e e e e e e m m m m m m m m m ...

Страница 129: ...ss 127 So the Exponent value is 10 The Mantissa is 11000010001110110111001 binary With the implied leading 1 the Mantissa is 1 611DB9 hex The Floating Point Representation is therefore 1 75871956 times 2 to the 10 Decimal equivalent 1800 929 NOTES Exponent the whole number before the decimal point Mantissa the positive fraction after the decimal point B 5 Modbus Register Map The Shark 100S meter s...

Страница 130: ...00 S Meter Modbus Map Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 131: ...9 M VAs 2 Block Size 6 read only 03E7 03E8 1000 1001 Volts A N FLOAT 0 to 9999 M volts 2 03E9 03EA 1002 1003 Volts B N FLOAT 0 to 9999 M volts 2 03EB 03EC 1004 1005 Volts C N FLOAT 0 to 9999 M volts 2 03ED 03EE 1006 1007 Volts A B FLOAT 0 to 9999 M volts 2 03EF 03F0 1008 1009 Volts B C FLOAT 0 to 9999 M volts 2 03F1 03F2 1010 1011 Volts C A FLOAT 0 to 9999 M volts 2 03F3 03F4 1012 1013 Amps A FLOA...

Страница 132: ...age FLOAT 9999 M to 9999 M watts 2 07DB 07DC 2012 2013 Negative VARs 3 Ph Average FLOAT 9999 M to 9999 M VARs 2 07DD 07DE 2014 2015 VAs 3 Ph Average FLOAT 9999 M to 9999 M VAs 2 07DF 07E0 2016 2017 Positive PF 3 Ph Average FLOAT 1 00 to 1 00 none 2 07E1 07E2 2018 2019 Negative PF 3 PF Average FLOAT 1 00 to 1 00 none 2 Block Size 20 read only 0BB7 0BB8 3000 3001 Volts A N Minimum FLOAT 0 to 9999 M ...

Страница 133: ...THD UINT16 0 to 9999 or 65535 0 1 1 0FA0 0FA0 4001 4001 Volts B N THD UINT16 0 to 9999 or 65535 0 1 1 0FA1 0FA1 4002 4002 Volts C N THD UINT16 0 to 9999 or 65535 0 1 1 0FA2 0FA2 4003 4003 Amps A THD UINT16 0 to 9999 or 65535 0 1 1 0FA3 0FA3 4004 4004 Amps B THD UINT16 0 to 9999 or 65535 0 1 1 0FA4 0FA4 4005 4005 Amps C THD UINT16 0 to 9999 or 65535 0 1 1 0FA5 0FA5 4006 4006 Phase A Current 0th har...

Страница 134: ...tatus7 UINT16 bit mapped 87654321 87654321 high byte is setpt 1 0 in 1 out low byte is setpt 2 0 in 1 out 1 1389 138A 5002 5003 Time Since Reset UINT32 0 to 4294967294 4 msec wraps around after max count 2 Block Size 4 write only 4E1F 4E1F 20000 20000 Reset Max Min Blocks UINT16 password 5 1 4E20 4E20 20001 20001 Reset Energy Accumulators UINT16 password 5 1 Block Size 2 read conditional write 55E...

Страница 135: ...e 1 7532 7532 30003 30003 PT denominator UINT16 1 to 9999 none 1 7533 7533 30004 30004 PT multiplier hookup UINT16 bit mapped mmmmmmmm MMMMhhhh MMMMmmmmmmmm is PT multiplier 1 10 100 1000 hhhh is hookup enumeration 0 3 element wye 9S 1 delta 2 CTs 5S 3 2 5 element wye 6S 1 7534 7534 30005 30005 Averaging Method UINT16 bit mapped iiiiii b sss iiiiii interval 5 15 30 60 b 0 block or 1 rolling sss su...

Страница 136: ...e 1 754B 754B 30028 30028 Limit 1 Identifier UINT16 0 to 65535 use Modbus address as the identifier see notes 7 11 12 1 754C 754C 30029 30029 Limit 1 Out High Setpoint SINT16 200 0 to 200 0 0 1 of full scale Setpoint for the above limit LM1 see notes 11 12 1 754D 754D 30030 30030 Limit 1 In High Threshold SINT16 200 0 to 200 0 0 1 of full scale Threshold at which above limit clears normally less t...

Страница 137: ...0014 40014 Volts B C UINT16 2047 to 4095 volts 1 9C4E 9C4E 40015 40015 Volts C A UINT16 2047 to 4095 volts 1 9C4F 9C4F 40016 40016 CT numerator UINT16 1 to 9999 none 1 9C50 9C50 40017 40017 CT multiplier UINT16 1 10 100 none 1 9C51 9C51 40018 40018 CT denominator UINT16 1 or 5 none 1 9C52 9C52 40019 40019 PT numerator UINT16 1 to 9999 none 1 9C53 9C53 40020 40020 PT multiplier UINT16 1 10 100 none...

Страница 138: ... data address exception if a write is attempted in an incorrect mode Entities to be monitored against limits are identified by Modbus address Entities occupying multiple Modbus registers such as floating point values are identified by the lower register address If any of the 8 limits is unused set its identifier to zero If the indicated Modbus register is not used or is a non sensical entity for l...

Страница 139: ...and Smart Grid Solutions C Shark 100S Meter DNP Map C 1 Introduction The Shark 100S meter s DNP map shows the client server relationship in the meter s use of DNP Protocol C 2 DNP Mapping DNP 1 to DNP 2 The Shark 100S DNP Point Map follows Binary Output States Control Relay Outputs Binary Counters Primary and Analog Inputs are described on Page 1 Internal Indication is described on Page 2 ...

Страница 140: ... 100 S Meter DNP Map Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 141: ...r 20 3 4 VAR hours Negative UINT32 0 to 99999999 VAR hr 20 4 4 VA hours Total UINT32 0 to 99999999 VA hr Read via Class 0 only 30 0 5 Meter Health SINT16 0 or 1 N A none 0 OK 30 1 5 Volts A N SINT16 0 to 32767 150 32768 V 30 2 5 Volts B N SINT16 0 to 32767 150 32768 V 30 3 5 Volts C N SINT16 0 to 32767 150 32768 V 30 4 5 Volts A B SINT16 0 to 32767 300 32768 V 30 5 5 Volts B C SINT16 0 to 32767 30...

Страница 142: ...mand SINT16 32768 to 32767 4500 32768 VA 30 20 5 Angle Phase A Current SINT16 1800 to 1800 0 1 degree 30 21 5 Angle Phase B Current SINT16 1800 to 1800 0 1 degree 30 22 5 Angle Phase C Current SINT16 1800 to 1800 0 1 degree 30 23 5 Angle Volts A B SINT16 1800 to 1800 0 1 degree 30 24 5 Angle Volts B C SINT16 1800 to 1800 0 1 degree 30 25 5 Angle Volts C A SINT16 1800 to 1800 0 1 degree 30 26 5 CT ...

Страница 143: ...ecting a PC to the meter using the meter s RS485 connection see Chapter 5 RS485 RS485 provides multi drop network communication capabilities Multiple meters can be placed on the same bus allowing for a Master device to communicate with any of the other devices Appropriate network configuration and termination should be evaluated for each installation to insure optimal performance see Chapter 5 Com...

Страница 144: ...Before confirmed communication with a master device the Data Link Layer must be reset This is necessary after a meter has been restarted either by applying power to the meter or reprogramming the meter The meter must receive a RESET command before confirmed communication can take place Unconfirmed communication is always possible and does not require a RESET User Data Function 3 After receiving a ...

Страница 145: ...should indicate it is both the first frame FIR 1 as well as the final frame FIN 1 D 4 Application Layer The Application Layer contains a header Request or Response Header depending on direction and data Application Headers Application Headers contain the Application Control Field and the Function Code Application Control Field Multiple fragment messages are not allowed for Shark 100S meters Each A...

Страница 146: ...tions Object 80 Direct Operate Function 5 Objects supporting the DIRECT OPERATE function are Control Relay Output Block Object 12 Direct Operate No Acknowledgment Function 6 Objects supporting the DIRECT OPERATE NO ACKNOWLEDGMENT function are Change to MODBUS RTU Protocol Response Function 129 Application responses from Shark 100 meters use the RESPONSE function Application Data Application Data c...

Страница 147: ...otocol State Energy Reset State Point 0 Shark 100S meters accumulate power generated or consumed over time as Hour Readings which measure positive VA Hours and positive and negative W Hours and VAR Hours These readings can be reset using a Control Relay Output Block object Object 12 The Binary Output Status point reports whether the Energy Readings are in the process of being reset or are accumula...

Страница 148: ... for the following purposes Energy Reset Change to MODBUS RTU Protocol Energy Reset Point 0 As stated previously Shark 100S meters accumulate power generated or consumed over time as Hour Readings which measure positive VA Hours and positive and nega tive W Hours and VAR Hours These readings may be reset using Point 0 Change to Modbus RTU Protocol Point 1 Refer to Section D 4 1 1 on the previous p...

Страница 149: ...mmunicate the following data measured by Shark 100S meters Hour Readings Hour Readings Points 0 4 NOTE These readings may be cleared by using the Control Relay Output Block see previous Section D 4 1 2 D 4 1 4 16 Bit Analog Input Without Flag Obj 30 Var 4 Analog Inputs support the following functions Read Function 1 A READ request for Variation 0 is responded to with Variation 4 Analog Inputs are ...

Страница 150: ...ency Three Phase Watts Max Avg Demand Three Phase VARs Max Avg Demand Three Phase Watts Max Avg Demand Three Phase VARs Max Avg Demand Three Phase VAs Max Avg Demand Angle Phase Power Angle Phase to Phase Voltage CT Numerator Multiplier Denominator PT Numerator Multiplier Denominator Health Check Point 0 The Health Check point is used to indicate problems detected by the Shark 100S meter A value o...

Страница 151: ... Points 4 6 These points are formatted as 2 s complement fractions They represent a fraction of a 300V Secondary input Inputs of above 30 V Secondary are pinned at 300V Secondary Phase Current Points 7 9 These points are formatted as 2 s complement fractions They represent a fraction of a 10A Secondary input Inputs of above 10A Secondary are pinned at 10A Secondary Total Power Points 10 11 Point R...

Страница 152: ...represents a fraction of 4500W Secondary in normal operation or 3000W Secondary in Open Delta operation Inputs above below 4500 or 3000W Secondary are pinned at 4500 or 3000W Secondary respectively Power Factor Point 13 This point is formatted as a 2 s complement integer It represents Power Factors from 1 000 0x0FC18 to 1 000 0x003E8 In Open Delta operation Total Power Factor Point 13 is always ze...

Страница 153: ... 3000W Secondary respectively Phase Angle Points 20 25 These points are formatted as 2 s complement integers They represent angles from 180 00 0x0F8F8 to 180 00 0x00708 CT PT Ratios Points 26 31 Point Reading 15 Maximum Positive Demand Total Watts 16 Maximum Positive Demand Total VARs 17 Maximum Negative Demand Total Watts 18 Maximum Negative Demand Total VARs 19 Maximum Average Demand VAs Point R...

Страница 154: ...d from mVs to thousands of kVs Following are example settings CT Example Settings 200 Amps Set the Ct n value for 200 and the Ct S value for 1 800 Amps Set the Ct n value for 800 and the Ct S value for 1 2 000 Amps Set the Ct n value for 2000 and the Ct S value for 1 10 000 Amps Set the Ct n value for 1000 and the Ct S value for 10 NOTE CT Denominator is fixed at 5 for 5A units CT Denominator is f...

Страница 155: ...16 Bit Analog Input Without Flags Object 30 Variation 4 Points 0 31 followed by 32 Bit Counters Without Flags Object 20 Variation 5 Points 0 4 followed by Binary Output Status Object 10 Variation 2 Points 0 1 There is NO Object 1 A request for Object 60 Variation 0 is treated as a request for Class 0 Data D 4 1 6 Internal Indications Obj 80 Var 1 Internal Indications support the following function...

Страница 156: ...0 Protocol Assignments Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions This page intentionally left blank ...

Страница 157: ...for installing the USB to IrDA Adapter E 2 Installation Procedures You can order CAB6490 from EIG s webstore www electroind com store Select Cables and Accessories from the list on the left side of the screen The USB to IrDA Adapter comes packaged with a USB cable and an Installation CD Follow this proce dure to install the Adapter on your PC 1 Connect the USB cable to the USB to IrDA Adapter and ...

Страница 158: ...n Power Monitoring and Smart Grid Solutions 5 Make sure the first Radio Button and the first Checkbox are selected as shown above These selections allow the Adapter s driver to be copied from the Installation disk to your PC 6 Click Next You will see the screen shown below 7 When the driver for the Adapter is found you will see the screen shown on the next page Select these options ...

Страница 159: ...nitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions 8 You do not need to be concerned about the message on the bottom of the screen Click Next to continue with the installation 9 You will see the two windows shown below Click Continue Anyway ...

Страница 160: ...The Leader In Power Monitoring and Smart Grid Solutions 10 You will see the screen shown below while the Adapter s driver is being installed on your PC 11 When driver installation is complete you will see the screen shown below 12 Click Finish to close the Found New Hardware Wizard IMPORTANT Do NOT remove the Installation CD until the entire procedure has been completed ...

Страница 161: ...rectly at the IrDA on the front of the Shark 100S meter It should be as close as possible to the meter and not more than 15 inches 38 cm away from it 14 The Found New Hardware Wizard screen opens again This time click the Radio Button next to Install the software automatically 15 Click Next You will see the screen shown below 16 Make sure the first Radio Button and the first Checkbox are selected ...

Страница 162: ...E 6 E Using the USB to IrDA Adapter CAB6490 Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions Electro Industries GaugeTech The Leader In Power Monitoring and Smart Grid Solutions ...

Страница 163: ...ions 17 When installation is complete you will see the screen shown below 18 Click Finish to close the Found New Hardware Wizard 19 To verify that your Adapter has been installed properly click Start Set tings Control Panel System Hardware Device Manager The USB to IrDA Adapter should appear under both Infrared Devices and Modems click on the sign to display all configured modems See the example s...

Страница 164: ...ay from the meter for a minute and then position it pointing at the IrDA again 20 Double click on the Standard Modem over IR link this is the USB to IrDA Adapter You will see the Properties screen for the Adapter 21 Click the Modem tab The Com Port that the Adapter is using is displayed in the screen 22 Use this Com Port to connect to the meter from your PC using the Communicator EXT software Refe...

Отзывы: