![Electro Industries Shark 100S Скачать руководство пользователя страница 105](http://html.mh-extra.com/html/electro-industries/shark-100s/shark-100s_installation-and-operation-manual_2379713105.webp)
Doc
#
E145721
7 - 5
7: Using the Submeter
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2. Press the Enter button from the Main Menu to view the Parameters screen for the
mode that is currently active.
7.2.3: Using Reset Mode
Reset mode has two options:
• Reset: Demand (rStd): resets the Max and Min values.
• Reset: Energy (rStE): resets the energy accumulator fields.
1. Press the Enter button while either rStd
or rStE is in the A window. The Reset
Demand No or Reset Energy No screen
appears.
• If you press the Enter button again,
the Main Menu appears, with the next
mode in the A window. (The Down
button does not affect this screen.)
• If you press the Right button, the
Reset Demand YES or Reset Energy
YES screen appears. Press Enter to
perform a reset.
NOTE: If Password protection is enabled
for reset, you must enter the four digit
password before you can reset the meter
(see Chapter 5 for information on Password protection). To enter a password, follow
the instructions in Section 7.2.4.
CAUTION! Reset Demand YES resets all Max and Min values.
2. Once you have performed a reset, the screen displays either “rSt dMd donE” or
“rSt EnEr donE”and then resumes auto-scrolling parameters.