![Electro Industries Shark 100S Скачать руководство пользователя страница 40](http://html.mh-extra.com/html/electro-industries/shark-100s/shark-100s_installation-and-operation-manual_2379713040.webp)
Doc
#
E145721
2 - 8
2: Meter Overview and Specifications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
128 bit WEP Encryption
128 bit Wireless Security
Modbus TCP Protocol
Mechanical Parameters
Dimensions:
(H7.9 x W7.6 x D3.2) inches,
(H200.7 x W193.0 x D81.3) mm
Weight:
4 pounds
KYZ/RS485 Port Specifications
RS485 Transceiver; meets or exceeds EIA/TIA-485 Standard:
Type:
Two-wire, half duplex
Min. Input Impedance:
96k
Ω
Max. Output Current:
±60mA
Wh Pulse
KYZ output contacts (and infrared LED light pulses through face plate; see Section 7.4
for Kh values):
Pulse Width:
40ms
Full Scale Frequency:
~6Hz
Contact type:
Solid State – SPDT (NO – C – NC)
Relay type:
Solid state
Peak switching voltage:
DC ±350V
Continuous load current:
120mA
Peak load current:
350mA for 10ms
On resistance, max.:
35
Ω
Leakage current:
1µA@350V
Isolation:
AC 3750V
Reset State:
(NC - C) Closed; (NO - C) Open