![Electro Industries Shark 100S Скачать руководство пользователя страница 143](http://html.mh-extra.com/html/electro-industries/shark-100s/shark-100s_installation-and-operation-manual_2379713143.webp)
Doc
#
E145721
D - 1
D: DNP 3.0 Protocol Assignments
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
D: DNP 3.0 Protocol Assignments
D.1: DNP Implementation
PHYSICAL LAYER
The Shark® 100S meter can use RS485 as the physical layer. This is accomplished by
connecting a PC to the meter using the meter’s RS485 connection (see Chapter 5).
RS485
RS485 provides multi-drop network communication capabilities. Multiple meters can
be placed on the same bus, allowing for a Master device to communicate with any of
the other devices. Appropriate network configuration and termination should be
evaluated for each installation to insure optimal performance (see Chapter 5).
Communication Parameters
Shark® 100S meters communicate in DNP 3.0 using the following communication
settings:
• 8 Data Bits
• No Parity
• 1 Stop Bit
• Baud Rates: 9600, 19200, 38400, 57600