2: Meter Overview and Specifications
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
Electro
Industries/GaugeTech
The Leader In Power Monitoring and Smart Grid Solutions
2.3: Compliance
• IEC 62053-22 (0.2% Accuracy)
• ANSI C12.20 (0.2% Accuracy)
• ANSI (IEEE) C37.90.1 Surge Withstand
• ANSI C62.41 (Burst)
• IEC1000-4-2: ESD
• IEC1000-4-3: Radiated Immunity
• IEC1000-4-4: Fast Transient
• IEC1000-4-5: Surge Immunity
• UL Listed
• CE Compliant
2.4: Accuracy
For 23
o
C, 3 Phase balanced Wye or Delta load, at 50 or 60 Hz (as per order), 5A
(Class 10) nominal unit:
Parameter
Accuracy
Accuracy Input Range
Voltage L-N [V]
0.1% of reading
2
(69 to 480)V
Voltage L-L [V]
0.1% of reading
(120 to 600)V
Current Phase [A]
0.1% of reading
1
(0.15 to 5)A
Current Neutral (calculated)
[A]
2.0% of Full Scale
1
(0.15 to 5)A @ (45 to 65)Hz
Active Power Total [W]
0.2% of reading
1,2
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
Active Energy Total [Wh]
0.2% of reading
1,2
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF
Reactive Power Total [VAR] 0.2% of reading
1,2
(0.15 to 5)A @ (69 to 480)V
@ +/- (0 to 0.8) lag/lead PF
Reactive Energy Total
[VARh]
0.2% of reading
1,2
(0.15 to 5)A @ (69 to 480)V
@ +/- (0 to 0.8) lag/lead PF
Apparent Power Total [VA] 0.2% of reading
1,2
(0.15 to 5)A @ (69 to 480)V
@ +/- (0.5 to 1) lag/lead PF