Technical Data
AEROTOP T20R-T35R
44
Heat pump type AEROTOP TR
T20R
T26R
T32R
T35R
Heating operation
For
A2/W35
Heating Capacity
Qh
KW
18.9 24.4 30.2 34.4
Power input
Pel
KW
5.8 7.4 8.8 9.2
Performance number EN14511
COP
-
3.2 3.3 3.4 3.6
Cooling operation
for A35/W18
Cooling Capacity
Qc
KW
20.2 30.6 34.7 36.6
Power input
Pel
KW
8.5 11.8 14 14.3
Condenser
Scroll hermetically
Maximum current consumption
Imax
A
16 22 27 25
Start-up current with smooth starter
VSA
A
40 55
67.5
62.5
Current intensity with blocked rotor
LRA
A
99 123 127 167
Current connection
V-f-Hz
400-3-50
Fuse WP
A/T
32 40 40 40
Condenser, heater side
Material: Chrome steel AISI 304, 1.4301
Hydraulic connections
IG
R"
1¼” 1¼” 1¼” 1¼”
Water content incl. connection hoses AEROTOP T
l
4.9 4.9 5.7 5.7
Volume stream heating operation nom/min
1)
l/h
3700/1714 5850/2259 6280/2803 7300/2964
Pressure loss heating operation
kPa
14.9/4.5 32.9/7.7 36.1/6.4 46.7/7
Minimum volume stream cooling operation (
∆
t= 5 K)
l/h
3470 5260 5970 6300
Pressure loss cooling operation
kPa
14 20.6
14.8 21.8
Max working pressure
p baar 10 10 10 10
Evaporator/fan
Volume stream
m
3
/h
7'300 8'200 10000 11000
Available pressure
2)
Pa
149 198 225 313
Power consumption fan
P
kW
0.530 0.700 0.500 0.650
Maximum current consumption fan
lmax
A
1.8 2.5 2.5 2.5
Coolant
-
R407C
Coolant filling AEROTOP TR
kg
16 16 21 21
Coolant circuit oil
-
Ester Oil
Oil quantity
l
4.1
4.1
4.1
4.1
Weight heat pump
kg
375
392
460
468
Sound Level
3)
Outdoor installation
Standard configuration with Hoods
4)
Lwa dB(A) 66.0 70.0 67.0 70.0
Sound Level
3)
Indoor setup
Sound power level On suction
Lwa
dB(A)
65.0 67.0 66.0 70.0
On exhaust
Lwa
dB(A)
59.0 61.0 64.0 67.0
Inside
Lpa
dB(A)
59.0 59.0 63.0 68.0
1) Min:
∆
t max= 10 K, with PHW-preparation
∆
tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*
∆
t[K]*
ρ
[kg/l])*3600).
2)
At maximum fan rotational speed.
3)
Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the
distance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to deter-
mine the noise level see planning documents.
4)
With Hl and HO Hoods