Initial Startup
AEROTOP T Checklist
37
Task
Check
Comment
Heat Pump
Define hydraulic scheme, select and compare with system:
-
Check hydraulic components
-
Overflow valve installed (50% overflow), acc. to system scheme
(systems with buffer storage and compact heat pump not required)
-
Check and adjust as needed consumer side (heater) pre-pressure expansion vessel
and water pressure and safety valve
-
Bleeding the system
-
Shutoff and cap valves open?
-
With non-compact HP: Heating water temperature >10°C?
Starting of the HP may be problematic, preheat buffer storage with e-rod!
-
Check pipe/tube dimensions
PWH storage:
-
Storage capacity:___ liters
-
Heat exchanger surface: ____ m
2
(>= 0.3 m
2
/kW)
Buffer storage:
- Correctly
connected?
-
Tank capacity:____ liters (30 l/kW with sep. storage)
Check electrical connections: (compare e-diagram with system)
-
Check cable entry points
-
Terminals: Check connections (tight enough?)
-
Check soft-starter (ampere and dip switches set correctly?)
-
Check rotary field and grounding conductor
- Correct
fuses?
-
Fuse protection force with all-pole disconnecting circuit breaker installed?
-
External e-rod fuse protection?
-
If electric company block exists, then disconnect via Logon B WP61
terminal X1 / L and 1 via contactor (not only with 3 phases)
-
Check all sensors (also those of HP) for proper fit and position (see electr. diagram
)
Initial Startup
Logon B WP61 configuration:
-
Configure controller acc. to diagram/scheme
-
Save sensor parameters! (Parameter 6200 "Configuration")
-
Query input/output test / check sensor values (line 7700 and up)
-
Conduct relay test using input/ output test Important: Do not allow evaporator
to start running! After test, reset parameter to "None"
-
Start heat pump (poss. change AT simulation parameter 7150 "Maintenance/Service")
Important: Reset to IBN!
-
Fill out initial startup record
Heat Source
-
Check fan speed setting.
-
Duct system open: No shaft coverings, blocked openings, etc.
-
Duct/shaft dirty, dusty, plugged with leaves, etc.
-
Protective grating installed
System/Unit:
Date: