Initial Startup
Fan Speed Setting
AEROTOP TC: Setting of the Integrated Thermal Valve
AEROTOP T
A Value
B Value
T35(R)
64 %
69 %
T32(R)
56 %
61 %
T26(R)
72 %
77 %
T20(R)
60 %
65 %
T16(R)
55 %
60 %
T14(R)
50 %
55 %
T12(R) / T12C
42 %
47 %
T10(X+R+RX) / T10C(X)
70 %
75 %
T07(X+R+RX) / T07C(X)
50 %
55 %
Fan Speed Settings
The fan speed of the air-water
AEROTOP T heat pumps can be
directly adjusted on the LOGON B
WP61 controller (parameter 3010).
The following table serves as a re-
ference for setting the fan speed based
on the most important setup variants:
•
A values refer to outdoor and
corner
setup.
•
B values refer to setups with air
duct on air intake and outlet
(KWI + KFS) or with rigid air ducts
(KSL).
Notes:
The setting must be increased by 5% if sound dampers are installed on the heat
pump. This applies usually to the AEROTOP T20 to T35 models.
Please contact the technical support if you have any additional questions.
AEROTOP TC Heat Pump:
Integrated Thermal Mixing Valve
The thermal mixing valve integrated
into the compact heat pump routes a
part of the flow water back to the buffer
storage tank only if the flow tempera-
ture is below +30°C. This means the
storage is heated immediately and the
energy depot is available for the de-
frosting process of the evaporator.
This upkeep function ensures a
continuous defrosting process and the
system can be operated even when
the heating system is cold.
Settings of the Integrated Thermal
Mixing Valve of the Heat Pumps
- AEROTOP
T07C
(manually
adjustable valve with scale):
The factory setting of this valve is set
with the scale to minimum (scale at 0)
= crank completely closed
Important: The line marking for the
adjustment is on the rear side of the
valve.
-
AEROTOP T10-12C (not manually
adjustable, must use key):
The following applies to correctly adjust
the setting: Open completely and then
close with 3½ turns. Important: Set like
this at the factory.
18