40
Technical Data
AEROTOP T T07(C)-T16
Model AEROTOP T
T07(C) T10(C) T12(C) T14
T16
Heating Cycle
Applies to all models at A2W35
Heating capacity/thermal rating
kW
6.4 9.1
11.8
13.7
14.8
Power consumption
kW
2.0 2.8 3.4
3.9 4.1
COP -
3.3 3.3 3.5
3.5 3.6
Compressor
Scroll hermetic
Max. current consumption
A
6.3 10 11 13 13.5
Starting current with soft starter
A
15.75 25 27.5
32.5
33.75
Current intensity with blocked rotor (LRA)
A
40 50 66
74 74
Electrical Connection
V-f-Hz
400-3-50
HP fuse
A/T 16 16 16 20 20
HP fuse with electr. heater element
A/T
20 20 20
25 25
Water Heat Exchanger
Material: chromium steel AISI 304 1.4301
Hydraulic Connections
R"
1” 1” 1”
1” 1”
Water volume incl. connection hoses AEROTOP TC
l 53 53
53
- -
Water volume incl. connection hoses AEROTOP T
l
2.6 3 3.1
3.4
3.4
Rated volume flow, heating nom/min
1)
l/h
1500/568 2100/835 2700/999
3070/1171
3100/1300
Pressure loss, heating
- AEROTOP TC (nom/min)
kPa
8.4/2.1
16.4/4.1
22.8/5.7
- AEROTOP T (nom/min)
kPa
28.3/4.4 32.9/4.1 33/4.5 36.5/4.6 35.5/5.5
Residual pressure AEROTOP TC
2)
kPa
51.4
57.9
55.4
Max working pressure
bar 3 3 3 3 3
Air Heat Exchanger/Fan
Volume flow
m3/h
2'500 3‘300 5'300
6'300
6'800
Available pressure
3)
Pa
150 92 146
112
82
Power consumption, fan
kW
0.035 0.100 0.100
0.170
0.210
Max current consumption, fan
A
1.6 1.6 2.1
2.1 2.1
Refrigerant
-
R407C
AEROTOP TC refrigerant charge
kg
1.9 2.95 3.7 -
-
AEROTOP T refrigerant charge
kg
2.5 3.1 3.7
4.1 4.1
Cooling circuit oil
-
Ester oil
Oil amount
l
1.1 1.36
1.85
1.65 1.89
Total weight, heat pump Aerotop TC
239 274 299 -
-
Total weight, heat pump Aerotop T
kg
204 246 272
276 279
Sound Level
4)
Outdoor installation
Standard configuration
5)
dB(A) 62.0 65.0 61.0 66.0 70.0
Sound Level
4)
Indoor setup
Sound power level On suction
dB(A) 53.0 56.0 54.0 59.0 61.0
On exhaust
dB(A) 48.0 53.0 50.0 53.0 55.0
Inside
dB(A) 50.0 54.0 55.0 60.0 60.0
1) Min:
∆
t max= 10 K, with PHW-preparation
∆
tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*
∆
t[K]*
ρ
[kg/l])*3600)
2)
Residual pumping pressure is stated for maximum pumping stage
3)
At maximum fan rotational speed.
4)
Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the dis-
tance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine
the noise level see planning documents.
5) With Rain Guard