42
Technical Data
AEROTOP T07(C)X-T10(C)X
Modell AEROTOP T…X
T07X (C)
T10X (C)
Heating Cycle
Applies to all models at A2W35
Heating capacity/thermal rating
kW
6.4 9.1
Power consumption
kW
2 2.8
COP -
3.3 3.3
Compressor
Hermetic scroll
Max. current consumption
A
17.3
23.5
Starting current with soft starter
A
40
40
Current intensity with blocked rotor (LRA)
A
76
114
Electrical Connection
V-f-Hz
230-1-50
Fuse
A/T 20
20
Fuse with electr. heater element: 2 kW
A/T
32 40
Fuse with electr. heater element: 4 kW
A/T
40 50
Fuse with electr. heater element: 6 kW
A/T 50
63
Water Heat Exchanger
Material: chromium steel AISI 304 1.4301
Hydraulic Connections
R"
1”
1”
Water volume incl. connection hoses AEROTOP TC
53
53
Water volume incl. connection hoses AEROTOP T
l
2.6
3
Rated volume flow, heating (nom/min.)
1)
l/h
1500/568 2100/835
Pressure loss, heating
- AEROTOP TC (nom/min.)
kPa
8.4/2.1 16.4/4.1
- AEROTOP T (nom/min.)
kPa
28.3/4.4 32.9/4.1
Residual pressure AEROTOP TC
2)
kPa
51.4 57.9
Max working pressure
bar
3 3
Air Heat Exchanger/Fan
Volume flow
m3/h
2'500 3‘300
Available pressure
3)
Pa
150 92
Power consumption, fan
kW
0.035 0.100
Rated current consumption, fan
A
1.6
1.6
Refrigerant
-
R407C
Refrigerant charge AEROTOP TCX
kg
1.9
2.95
Refrigerant charge AEROTOP TX
2.5
3.1
Cooling circuit oil
-
Ester oil
Oil amount
l 1.1
1.36
Total weight, heat pump
AEROTOP TC
kg
242
278
AEROTOP T
207
250
Sound Level
4)
Outdoor installation
Standard configuration
5)
dB(A)
62.0 65.0
Sound Level
4)
Indoor setup
Sound power level On suction
dB(A)
53.0 56.0
On exhaust
48.0 53.0
Inside
50.0 54.0
1) Min:
∆
t max= 10 K, with PHW-preparation
∆
tmax = 5 K. (V' [l/h]= Qh[kW]/(4.18*
∆
t[K]*
ρ
[kg/l])*3600)
2)
Residual pumping pressure is stated for maximum pumping stage
3)
At maximum fan rotational speed.
4)
Measuring according to DIN ISO 9614-2. Sound power level is a property of the source of noise and therefore dependent on the dis-
tance; it describes the totality of the sound power of the corresponding source radiating in all directions. Information to determine
the noise level see planning documents.
5) With Rain Guard