FIREFRONT

This fire is supplied with a particular style of firefront. Use of the firefront will ensure an adequate
airflow under the firebed for the correct functioning of this appliance.

Compliance with safety standards cannot be guaranteed if another style of front is used.

CLEARANCES TO COMBUSTIBLES

A combustible shelf may be fixed to the wall above the fire, providing that it complies with the
dimensions given below.

A non-combustible shelf may be fitted to within 10mm of the top edge of the fireframe.
Combustible materials, such as wood, may be fitted to within 100mm (4in) of either side of the
frame of the appliance, providing the forward projection does not exceed 100mm (4in).
Any combustible side walls must be at least 500mm to the side of the radiant heat source.
As with all heating appliances, any decorations, soft furnishings, and wall coverings (i.e. flock,
blown vinyl and embossed paper) positioned too close to the appliance may discolour or scorch.

VENTILATION

No purpose provided ventilation is normally required for this appliance

.

The requirements of

other appliances operating in the same space or room, and the results of a spillage test must be
taken into consideration when assessing ventilation requirements, this will have been carried out
by your CORGI registered installer.

For Republic of Ireland, ventilation may be required, see IS 813, ICP3, IS 327, and any other rules
in force.

OPERATING INSTRUCTIONS

Turn on the power supply and momentarily press the ON switch on the control box. The fan
should operate with the warning light illuminated. After a very short time the fan will run at nor-
mal speed and a click may be heard as the safety solenoid opens. The warning light should extin-
guish.

The pilot is visible through the underside of the left hand front
coal strip. Push in and turn the control knob to the SPARK posi-
tion, and hold there for a few seconds. Continue turning anti-
clockwise through the spark click to the PILOT light position,
ensuring the pilot has lit. If not, return the knob clockwise, and
repeat.

When the pilot lights after the spark, keep the knob depressed
for approximately ten seconds. Now release the knob and the
pilot should stay alight. If not, repeat ignition. If the pilot is
extinguished 

during use

, wait three minutes before repeating

the ignition procedure. To achieve the HIGH setting, push the control knob in slightly and con-
tinue turning anti-clockwise to the high position. The main burner should light after a few sec-
onds. To decrease the setting to LOW, turn the control knob clockwise to the low setting. To turn
to the PILOT position from the HIGH or LOW positions, press the control knob in, and return to
the pilot position and release.

To turn the fire OFF, keep the knob pressed in, return to the off position and release. Press the
OFF button on the control box to switch off the fan.

2

2.0

3.0

4.0

5.0

Maximum depth of shelf                    Minimum distance from finished hearth

surface to underside of shelf

100mm (4in)

745mm (29 1/4 in)

150mm (6in)

845mm (33 1/4 in)

203mm (8in)

895mm (35 1/4 in)

©

2009 Focal Point Fires plc.

Содержание eko 3021

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 3021 eko 3031 fan flue fuel effect gas fire...

Страница 2: ...h of at least 300mm depth This appliance is factory set for operation on the gas type and at the pressure stated on the appliance data plate This appliance is available with a number of fuel effect op...

Страница 3: ...iance Data Installation Requirements Terminal Location Site Requirements Ventilation Unpacking the Appliance Component Checklist Preparing for Installation Outer Wall Aperture Gas Supply Routing Insta...

Страница 4: ...ges and car ports then further advice should be sought from CORGI or the manufacurer 2 APPLIANCE DATA Eko 3021 models Eko 3031 models Gas Group G20 Natural Gas CAT I2H G20 Natural Gas CAT I2H Inlet Pr...

Страница 5: ...f protecting this type of roof from heat build up TERMINAL LOCATION Minimum location distances A 300mm above ground level roof or balcony level B 200mm below balconies or car ports C 1500mm vertically...

Страница 6: ...or fixed fender of at least 50mm high The non combustible hearth must extend a minimum of 300mm in front of and 150mm either side of the live part of the appliance The hearth must therefore be a mini...

Страница 7: ...amic fibre combustion matrix 1 Terminal guard cage 1 Front coal piece Eko 3031 models 1 Fan box cover 1 Bag of 11 moulded coals Eko 3021 coal models 1 Fan box trim 1 Bag of 16 moulded ceramic coals Ek...

Страница 8: ...diameter aperture centred around the pilot hole If the fan terminal is to be recessed into the outer leaf the hole should be opened up to the dimensions given in the diagram Clear all the brick rubble...

Страница 9: ...future installation of cavity wall insulation from coming into contact with hot areas of the appliance At this point the false chimney breast or fire surround should be installed Note When constructi...

Страница 10: ...occupants and protect any other parts of the building against dust infiltration Areas that are opened up will need to be protected against rain or snow during the work and if there is a risk of frost...

Страница 11: ...are is taken to prevent combustible materials from contact with hot surfaces The appliance must be installed in accordance with British Gas documents DM2 and DM3 or the Institute of Gas Engineers publ...

Страница 12: ...r wall from the heat effect of the flue It may be advantageous to use a sheet of Superlux board for this purpose Installation by setting the appliance into the inner leaf of wall When setting the appl...

Страница 13: ...feed through the back of the firebox and fit the grommet seal if applicable Now carefully slide the appliance back into position and secure into place using the two previously drilled holes Ensure the...

Страница 14: ...res in the sides of the fan terminal MUST be allowed to vent to the cavity to aid cooling of components within With the terminal fixed into position the wires may now be connected Attach the green ear...

Страница 15: ...ainst the side cheeks as shown in the photograph If necessary pull the coals forward slightly to ensure their rear edges do not overhang the flame ports The edges of the coals MUST NOT be allowed to e...

Страница 16: ...3 Open the bag of 16 moulded coals All of the coals are the same Take five coals and place them as shown Care should be taken to ensure that the coals bridge the gap between the front coal and the fou...

Страница 17: ...sembled according to the instructions Never add to the sixteen coals or change them for a different type Never throw rubbish or other matter onto the coal bed FUELBEDLAYOUT Eko 3031 MODELS Pebble Effe...

Страница 18: ...d according to the instructions Never add to the sixteen pebbles or change them for a different type Never throw rubbish or other matter onto the fuel bed Due to the light colour of the pebbles some d...

Страница 19: ...he control knob in and return to the pilot position and release To turn the fire OFF keep the knob pressed in return to the off position and release Press the OFF button on the control box to switch o...

Страница 20: ...smoke match across the opening All the smoke should be drawn into the upper firebox Any smoke returning into the room indicates that spillage is occurring If the initial test fails run the fire for a...

Страница 21: ...see the relevant sections CLEANING THE CERAMICS Remove the firefront and place to one side Remove the ceramic components Gently clean in the open air Be careful not to create dust from the coals Where...

Страница 22: ...an Press the ON switch the fan should build up speed with the warning light illuminated and then rest at normal operating speed The light on the control box should extinguish The safety solenoid on th...

Страница 23: ...effect of extractor fans Fan runs but pilot flame will not hold Loose thermocouple connection in rear of gas valve when control knob is released Check pilot flame is engulfing tip of thermocouple Pil...

Страница 24: ...firm are concerned Combustible items such as flooring and furniture and soft wall coverings such as flock blown vinyl or embossed paper may discolour if fitted too close to the fire See relevant secti...

Страница 25: ...on the power supply and momentarily press the ON switch on the control box The fan should operate with the warning light illuminated After a very short time the fan will run at nor mal speed and a cl...

Страница 26: ...e may damage the finish To re assemble ensure the magnets are place on the steel backing pieces and re fit to the firebox IMPORTANT Due to the possibility of sharp edges care should be taken when clea...

Отзывы: