background image

INSTALLATION METHOD 2  (continued)

It is essential the Rockwool pad be fitted to the rear of the appliance to prevent condensation
and to insulate the appliance firebox from the cold air of the cavity.

Note: Neither the appliance nor the Rockwool insulating pad should bridge the cavity.
Consult your local Building Control Department for any additional construction require-
ments or further advice

.

INSTALLATION METHOD 3

Installation into timber framed dwellings

Where removal of any part of the inner timber leaf of the wall is involved, the structural integrity
of the wall must be maintained and the advice of your local Building Control Department should
be sought. If the property is under any N.H.B.C. cover, it is advised that their advice on this mod-
ification should also be sought.

Either of the two preceding methods of installation may be adapted for use in timber framed
buildings, providing extra care is taken to prevent combustible materials from contact with hot
surfaces.The appliance must be installed in accordance with British Gas documents DM2 and DM3
or the Institute of Gas Engineers published procedure IGE/UP/7.

Special attention must be paid to the location of the studwork frames of the inner leaf and the
appliance positioned accordingly. Wires and pipes that run within the inner timber leaf must also
be located and taken into account when positioning the appliance.

9

Outer cavity leaf

Inner cavity leaf

Lintel

Superlux board

Fireplace backpanel

B

A

C

D

F

E

A- Opening width: (Eko 3021 380mm min 450mm max) (Eko 3031 375mm min. 460mm max).
B- Overall width: (Eko 3021 and Eko 3031 480mm)
C- Overall height (exc hearth): (Eko 3021 and Eko 3031 590mm)
D- Opening height: (exc hearth): (Eko 3021 540mm min 580mm max) (Eko 3031 565mm min. 580mm max)
E- Recessed depth of fire: (Eko 3021 125mm) (Eko 3031 180mm)
F- The hearth must extend 300mm in front of the appliance, with it’s top surface 50mm above the surrounding
floor level or having a 50mm high fixed fender around it’s perimeter.

8.4

8.5

©

2009 Focal Point Fires plc.

Содержание eko 3021

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 3021 eko 3031 fan flue fuel effect gas fire...

Страница 2: ...h of at least 300mm depth This appliance is factory set for operation on the gas type and at the pressure stated on the appliance data plate This appliance is available with a number of fuel effect op...

Страница 3: ...iance Data Installation Requirements Terminal Location Site Requirements Ventilation Unpacking the Appliance Component Checklist Preparing for Installation Outer Wall Aperture Gas Supply Routing Insta...

Страница 4: ...ges and car ports then further advice should be sought from CORGI or the manufacurer 2 APPLIANCE DATA Eko 3021 models Eko 3031 models Gas Group G20 Natural Gas CAT I2H G20 Natural Gas CAT I2H Inlet Pr...

Страница 5: ...f protecting this type of roof from heat build up TERMINAL LOCATION Minimum location distances A 300mm above ground level roof or balcony level B 200mm below balconies or car ports C 1500mm vertically...

Страница 6: ...or fixed fender of at least 50mm high The non combustible hearth must extend a minimum of 300mm in front of and 150mm either side of the live part of the appliance The hearth must therefore be a mini...

Страница 7: ...amic fibre combustion matrix 1 Terminal guard cage 1 Front coal piece Eko 3031 models 1 Fan box cover 1 Bag of 11 moulded coals Eko 3021 coal models 1 Fan box trim 1 Bag of 16 moulded ceramic coals Ek...

Страница 8: ...diameter aperture centred around the pilot hole If the fan terminal is to be recessed into the outer leaf the hole should be opened up to the dimensions given in the diagram Clear all the brick rubble...

Страница 9: ...future installation of cavity wall insulation from coming into contact with hot areas of the appliance At this point the false chimney breast or fire surround should be installed Note When constructi...

Страница 10: ...occupants and protect any other parts of the building against dust infiltration Areas that are opened up will need to be protected against rain or snow during the work and if there is a risk of frost...

Страница 11: ...are is taken to prevent combustible materials from contact with hot surfaces The appliance must be installed in accordance with British Gas documents DM2 and DM3 or the Institute of Gas Engineers publ...

Страница 12: ...r wall from the heat effect of the flue It may be advantageous to use a sheet of Superlux board for this purpose Installation by setting the appliance into the inner leaf of wall When setting the appl...

Страница 13: ...feed through the back of the firebox and fit the grommet seal if applicable Now carefully slide the appliance back into position and secure into place using the two previously drilled holes Ensure the...

Страница 14: ...res in the sides of the fan terminal MUST be allowed to vent to the cavity to aid cooling of components within With the terminal fixed into position the wires may now be connected Attach the green ear...

Страница 15: ...ainst the side cheeks as shown in the photograph If necessary pull the coals forward slightly to ensure their rear edges do not overhang the flame ports The edges of the coals MUST NOT be allowed to e...

Страница 16: ...3 Open the bag of 16 moulded coals All of the coals are the same Take five coals and place them as shown Care should be taken to ensure that the coals bridge the gap between the front coal and the fou...

Страница 17: ...sembled according to the instructions Never add to the sixteen coals or change them for a different type Never throw rubbish or other matter onto the coal bed FUELBEDLAYOUT Eko 3031 MODELS Pebble Effe...

Страница 18: ...d according to the instructions Never add to the sixteen pebbles or change them for a different type Never throw rubbish or other matter onto the fuel bed Due to the light colour of the pebbles some d...

Страница 19: ...he control knob in and return to the pilot position and release To turn the fire OFF keep the knob pressed in return to the off position and release Press the OFF button on the control box to switch o...

Страница 20: ...smoke match across the opening All the smoke should be drawn into the upper firebox Any smoke returning into the room indicates that spillage is occurring If the initial test fails run the fire for a...

Страница 21: ...see the relevant sections CLEANING THE CERAMICS Remove the firefront and place to one side Remove the ceramic components Gently clean in the open air Be careful not to create dust from the coals Where...

Страница 22: ...an Press the ON switch the fan should build up speed with the warning light illuminated and then rest at normal operating speed The light on the control box should extinguish The safety solenoid on th...

Страница 23: ...effect of extractor fans Fan runs but pilot flame will not hold Loose thermocouple connection in rear of gas valve when control knob is released Check pilot flame is engulfing tip of thermocouple Pil...

Страница 24: ...firm are concerned Combustible items such as flooring and furniture and soft wall coverings such as flock blown vinyl or embossed paper may discolour if fitted too close to the fire See relevant secti...

Страница 25: ...on the power supply and momentarily press the ON switch on the control box The fan should operate with the warning light illuminated After a very short time the fan will run at nor mal speed and a cl...

Страница 26: ...e may damage the finish To re assemble ensure the magnets are place on the steel backing pieces and re fit to the firebox IMPORTANT Due to the possibility of sharp edges care should be taken when clea...

Отзывы: