VENTILATION

No purpose provided ventilation is normally required for this appliance. The requirements of
other appliances operating in the same room or space must be taken into consideration when
assessing ventilation.

If spillage is detected when commissioning the appliance then amongst other problems there may
be insufficient natural ventilation for the correct operation of the flue. This is potentially a greater
problem should the property be of modern nature. If the appliance does not spill with windows
open but does with windows closed, this proves that lack of ventilation is the problem, if not, it
will be the flue at fault. Installation of an air brick is the best solution. Any ventilation fitted must
comply with BS 5871 part 2 and BS 5440 part 2.

Spillage detected during commissioning is almost always a result of poor flue performance, which
cannot be corrected by any amount of ventilation.

For Republic of Ireland ventilation may be required, see IS 813, ICP3, IS 327, and any other rules
in force.

PREFABRICATED FLUE BOXES

This appliance can be fitted into a number of proprietory flue boxes, provided that the minimum
dimensions given in the diagram below are complied with. The flue outlet of the fire 

must not

obscure the flue outlet from the flue box. A smooth path into the flue must exist.

Constructional Note: 

The frame of the fire, any back panel or other infill panel, and the flue box

must be sealed together so that there is no possibility of leakage between them. Adequate clear-
ances to combustible materials (e.g. false chimney breast construction) must be maintained.

The manufacturers’ instructions for the fitting of the prefabricated flue box shall be com-
plied with at all times.

Some flue boxes may require minor adaption when fitting the fire using the cable fixing kit.
The firebox, base of the flue box, and the hearth may be drilled to allow plugs and screws to
secure installation.

It is important that the sealing requirements of the appliance are met at all times and that the flue
box is well sealed to any back or infill panel.

Note: The DEPTH dimensions shown are inclusive of any back or infill panels.

4

5.0

175mm min internal
dia twin wall flue tube

210mm min depth

400 mm min
opening width

540mm min
opening height

6.0

©

2009 Focal Point Fires plc.

Содержание eko 2010

Страница 1: ...installation and user instructions All instructions must be handed to user for safekeeping Revision A 06 09 Country s of destination GB IE eko 2010 eko 2020 fuel effect gas fire...

Страница 2: ...ppliance is factory set for operation on the gas type and at the pressure stated on the appli ance data plate This appliance is available in either a manual control version or a battery powered remote...

Страница 3: ...is appliance features a battery opearated remote control system and under normal usage will need new batteries approximately every twelve months Remote control Handset requirements 1 x PP3 type 9 volt...

Страница 4: ...is installed into and the one venting the gases into the air A suitable ter minal may be fitted such as class GC1 as regulations allow This appliance is suitable for use with a lightweight surround an...

Страница 5: ...e providing that it complies with the dimensions given below A non combustible shelf may be fitted to within 10mm of the top edge of the fireframe Combustible materials such as wood may be fitted to w...

Страница 6: ...s appliance can be fitted into a number of proprietory flue boxes provided that the minimum dimensions given in the diagram below are complied with The flue outlet of the fire must not obscure the flu...

Страница 7: ...x PP3 4 x AA remote control option only 1 Self tapping screw pack 3 Lengths of self adhesive sealing strip 1 Rubber grommet PREPARING THE APPLIANCE Note Ensure that the gas supply is isolated before...

Страница 8: ...ot outlet of the firebox is not restricted in any way Remove the firebox and take any necessary measurements before making good and prepar ing for final installation CABLE FIXING For fixing of the fir...

Страница 9: ...ayout given the eyebolts should be posi tioned as close to the correct layout as possible Before finally fitting cables ensure the self adhesive sealing strips are in position on the back of the appli...

Страница 10: ...plate is not already fitted attach with two screws ensuring the control knob is free to be depressed fully FUEL BED LAYOUT Coal Effect Option 1 Remove the combustion matrix from its pro tective packag...

Страница 11: ...ain remember not to push the coals down too far into the valleys between the coal supports as this can have a detri mental effect to the flame picture 5 Now take another six coals and place behind the...

Страница 12: ...o be taken not to push the pebbles right down between the supports as this can affect the flame picture when the appliance is running 3 Take five more ceramic pebbles and posi tion as shown to form th...

Страница 13: ...inishes The frame is of three piece design and is held onto the firebox by magnets Firstly attach two magnets one at the top and one at the bot tom to each side piece and then attach to the sides of t...

Страница 14: ...e control versions The gas valve has two control knobs Turn the main burner control shown on left hand side of control valve knob fully anti clockwise Turn ignition knob shown on right hand side of co...

Страница 15: ...pressure is acceptable then a problem in the supply pipework is to be suspected This will be dirt and debris kinked or inadequate size pipes restriction in a fitting or solder flashing across a joint...

Страница 16: ...r servicing Frequency of service depends on usage but MUST be carried out at least one annually Scratched and other superficial damage to the matt black paintwork of the appliance can be cov ered with...

Страница 17: ...g further Check the seal around the fire frame and replace if necessary Refitting of the firebox is described in the relevant section DISMANTLING THE BURNER TRAY Remove the tray as previously describe...

Страница 18: ...and then cuts off Excessive room draught or flue pull rectify Loose or faulty thermocouple rectify ODS system in operation Firebox grommet seal not fitted rectify Lint in pilot aeration hole clean th...

Страница 19: ...foreign material on this fire the fuel effect must be of the correct type and laid out in accordance with the relevant section of these instructions Failure to do so could create a hazard or lead to s...

Страница 20: ...t by your CORGI registered installer For Republic of Ireland ventilation may be required see IS 813 ICP3 IS 327 and any other rules in force OPERATING INSTRUCTIONS manual versions The pilot is visible...

Страница 21: ...n inbuilt safety feature to pre vent the main burner being activated or turned up accidentally It is nec essary to press button 1 and 2 see illustration simultaneously to turn the fire up To turn the...

Страница 22: ...COALS AND CERAMICS See the relevant section in the Installation Guide of these instructions Do not create dust from the coals Clean gently in the open air Replace components with original spares only...

Отзывы: