P/N 3100346 ISSUE 3 © 2003
Installation Instructions for Adaptatone Millennium Tone Generator Series 5540M-485
and Tone Generator with Voice Messaging Series 5540MV-485 and
Speaker/Amplifier, Series 5532
Description and Operation
Description and Operation
Description and Operation
Description and Operation
Description and Operation
Edwards Tone Generator and Speaker/Amplifiers are
intended for industrial applications where high audible
output and microcomputer reliability are required.
Catalog Series 5532M ending with suffixes -AQ, -24AQ,
-Y6 or -24Y6 are CE Marked. Additionally, the Adaptatone
Millennium series are UL and cUL Listed as Audible Signal
Appliances for use in the following hazardous locations.
Electrical Specifications
Electrical Specifications
Electrical Specifications
Electrical Specifications
Electrical Specifications
Input Board
Main Power
Catalog
Current (A)
Number
Voltage Current
Voltage
Standby
Tone On
Tone Generator
5540M-485Y6
24V DC
6 mA
125V DC**
0.10
0.21
5540MV-485Y6
250V DC**
0.02
0.10
120V AC 50/60 Hz
0.10
0.32
240V AC 50/60 Hz
0.10
0.20
Speaker/Amplifier - Standard Volume
5532M-AQ
24V DC
0.10
0.74
24V AC 50/60 Hz
0.10
1.3
5532M-N5
120V AC 50/60 Hz
0.10
0.36
5532M-Y6
125V DC**
0.10
0.21
250V DC**
0.02
0.10
120V AC 50/60 Hz
0.10
0.32
240V AC 50/60 Hz
0.10
0.20
5532B-AQ
24V DC
0.06
0.69
36V DC
0.07
0.84
24V AC 60 Hz
0.26
1.36
24V AC 50 Hz
0.26
1.36
5532B-N5
120V AC 60 Hz
0.10
0.29
120V AC 50 Hz
0.09
0.29
5532B-Y6
125V DC**
0.05
0.16
250V DC**
0.04
0.10
120V AC 60 Hz
0.10
0.29
240V AC 60 Hz
0.11
0.23
120V AC 50 Hz
0.09
0.29
240V AC 50 Hz
0.10
0.22
Speaker/Amplifer - High Volume
5532MHV-AQ
24V DC
0.10
1.5
24V AC 50/60 Hz
0.10
2.3
5532MHV-Y6
125V DC
0.10
0.39
250V DC
0.02
0.19
120V AC 50/60 Hz
0.10
0.56
240V AC 50/60 Hz
0.10
0.34
5532BHV-AQ
24V DC
0.06
1.51
36V DC
0.07
1.98
24V AC 60 Hz
0.26
1.86
24V AC 50 Hz
0.26
1.86
5532BHV-Y6
125V DC
0.05
0.25
250V DC
0.04
0.23
120V AC 60 Hz
0.10
0.62
240V AC 60 Hz
0.11
0.33
120V AC 50 Hz
0.09
0.62
240V AC 50 Hz
0.10
0.33
*5532M-Y6 is suitable for use with 120/240V AC Main Power input in conjunction
with the 5541M-Y6 Millennium System Master either for emergency/evacuation,
non-fire, or for supplementary fire alarm control panel accessory applications (see
instructions for 5541M-Y6, part 3100471).
The 5532B Speaker/Amplifiers are UL Listed and CSA Cer-
tified as Audible Signaling Appliances.
The 5532M-Y6 is additionally UL Listed in a Speaker and
Amplifier category, when powered with 120V/240V AC
50/60 Hz, for use in conjunction with the 5541M-Y6 Mil-
lennium System Master either for emergency/evacuation,
non-fire, or for supplementary fire alarm control panel
accessory applications (see Instructions for 5541M-Y6,
part 3100471).
The Tone Generator operates from local power. It accom-
modates up to four normally-open contacts on its inputs.
The tone that sounds in response to an active input is
determined by setting miniature programming switches
inside the unit. Figure 19 has switch settings for setting
tones.
Four tones may be programmed into the Tone Generator
at any time. These tones operate on a pyramid-type pri-
ority system. The tone programmed on SW1 overrides
the tones programmed on SW2, SW3, and SW4. The tone
on SW2 overrides the tones programmed on SW3 and SW4.
Likewise, the tone on SW3 overrides the tone programmed
on SW4. The tone programmed on SW4 has the lowest
priority and cannot override any other programmed tone.
Speaker/Amplifiers are heavy-duty, stand-alone signaling
devices that operate from local power and sound a tone
programmed at the Tone Generator. Speaker direction
and the output level are easily adjustable.
Specifications
Specifications
Specifications
Specifications
Specifications
Weight - Tone Generator ....................... 6 Pounds (2.7 kg)
Weight - Speaker/Amplifier .................. 9 Pounds (4.1 kg)
Hazardous Locations, UL Standard UL1604
Ambient Temp. ................... +41F to +104F (+5C to +40C)
Non-Hazardous Locations
Variable Ambient Temp. ..... -40F to +151F (-40C to +66C)
Hazardous Locations and Variable Ambient Conditions apply only
where UL listings are accepted and do not apply to either CE confor-
mity or TUV-Rheinland Certification.
Catalog
Hazardous
Temp.
Number
Locations
Code
5532M-AQ
Class I, Div. 2, Groups A, B, C, D
T4 (135C)
5532M-N5
Class II, Div. 2, Groups F, G
T5 (100C)
5532M-Y6
Class III, Div. 1 and 2
5532MHV-AQ
5532MHV-Y6
5540M-485Y6
Class I, Div. 2, Groups A, B, C, D
T4 (135C)
5540MV-485Y6
Class II, Div. 2, Groups F, G
T5 (100C)
Class III, Div. 1 and 2