background image

P/N 3100346  ISSUE 3

PAGE 6

<ZONE>

Programmable unit Zone issued by the master or controlling computer
Range ASCII A-D (1 byte). Note – Zone value is not retained after power loss unless

battery backup is installed. Value defaults to Zone A on power up.

<ETX>

The <ETX> character has a value of 3 hexadecimal and is required at the end of

every message (1 byte)

<CHKSUM>

Optional two byte Message Block checksum (2 bytes).  Refer to Section 4.0 for

Block checksum calculation and verification. If checksum is not desired, must pad

these two bytes with two ASCII zeros 00.

3.0

Message Command Set

3.1

Tone/Message Command  - 00-1F
Send Format:  <STX><UA><TONE> <TIME> <ZONE> <ETX> <CHKSUM>

<UA>

Unit address characters (2 bytes). See Section 2.0, Messaging Format

<TONE>

Tone/Message to be played by the unit. Example - If tone 06 is chosen, the two

byte <TONE> data field should contain ASCII ‘0’ and ‘6’ written in ASCII format as

06. Range ASCII 00-1F(2 bytes). See Tone Chart for a list of available tones or

messages.

<TIME>

Time sequence for Tone/Message to be played (00-99 seconds). For continous play

of Tone/Message, use ‘00’ in this data field. Range ASCII 00-99 (2 bytes)

<ZONE>

Units matching this zone field will play Tone/Message indicated in the <TONE>

data field for specified time indicated in <TIME> data field. All other zones remain

in standby mode.

<ETX>

The <ETX> character has a value of 3 hexadecimal and is required at the end of

every message (1 byte)

<CHKSUM>

Optional two byte Message Block checksum (2 bytes).  Refer to Section 4.0 for

Block checksum calculation and verification. If checksum is not desired, must pad

these two bytes with two ASCII zeros 00.

3.2

BROADCAST COMMAND  - 41
Send Format:  <STX> 41 <TONE> <TIME> <ZONE> <ETX> <CHKSUM>

<41>

In this command type, two byte ASCII ‘41’ replaces <UA> characters. This command

is issued to all units containing the identical <ZONE> field.

<TONE>

Tone/Message to be played by the unit. See tone chart for a list of available tones/

messages. Range ASCII 00-1F (2 bytes).

<TIME>

Time sequence for Tone/Message (00-99 seconds). For continous play of Tone/

Message, use ‘00’ in this data field. Range ASCII 00-99 (2 bytes)

<ZONE>

Units matching this zone field will play Tone/Message indicated in the <TONE>

data field for specified time indicated in <TIME> data field. All other zones remain

in standby mode.

<ETX>

The <ETX> character has a value of 3 hexadecimal and is required at the end of

every message (1 byte)

<CHKSUM>

Optional two byte Message Block checksum (2 bytes).  Refer to Section 4.0 for

Block checksum calculation and verification.  If checksum is not desired, must pad

these two bytes with two ASCII zeros 00.

Unit Response: None

Example:

<STX>410530B<ETX>00
Units programmed with Zone ‘B’ only to play Tone 05 for 30 seconds then shut off

automatically. Checksum characters not used in this example.

Note: 

do not use spaces between message characters in the above example.

3.3

POLL COMMAND and SET UNIT ZONE  - 43
Send Format:

<STX><UA>43<00><ZONE><ETX><CHKSUM>

<UA>

Unit address, ASCII Range 00-1F (two bytes)

<43>

Two byte ASCII Command denoting POLL Command or Zone Assignment (2 byte).

Содержание 5532M-AQ

Страница 1: ...Millennium System Master either for emergency evacuation non fire or for supplementary fire alarm control panel accessory applications see instructions for 5541M Y6 part 3100471 The 5532B Speaker Ampl...

Страница 2: ...zed 5 Adjust the volume as necessary Set the main volume using the potentiometer on the main board Figures 13 14 and 15 and then set the voice volume using the potentiometer on the voice module board...

Страница 3: ...Speaker Amplifier Audio Coupler Board Use shielded cable and connect braid or drain to earth ground wire lead of 5540 Tone Generator c Connect incoming power to wire leads using a butt splice or other...

Страница 4: ...r using 4 retained cover screws 9 Torque signal box cover screws to a minimum of 20 in lbs 10 Verify operability Maintenance and Maintenance and Maintenance and Maintenance and Maintenance and T T T T...

Страница 5: ...g Baud Rate S1 6 S1 7 1200 OPEN OPEN 2400 CLOSED OPEN 9600 OPEN CLOSED 19200 CLOSED CLOSED 1 4 Set 100 ohm termination resistor if required Network termination is required if the unit is located at th...

Страница 6: ...Optional two byte Message Block checksum 2 bytes Refer to Section 4 0 for Block checksum calculation and verification If checksum is not desired must pad these two bytes with two ASCII zeros 00 3 2 B...

Страница 7: ...ETX The ETX character has a value of 3 hexadecimal and is required at the end of every message 1 byte CHKSUM Receiving unit calculates two byte checksum and returns ASCII value Refer to Section 4 0 fo...

Страница 8: ...X 00 9 seconds after issuing command from above the master issues the Time Remaining Command 44 Command STX 1F4400A ETX 00 and the unit replies with the following message Reply STX 1F445A ACK ETX 5E V...

Страница 9: ...energizes relay for 5 seconds then shut off automatically Checksum characters not used in this example UA Unit address 31 Two byte ASCII Command 31 echoed back from receiving unit TIME Received two by...

Страница 10: ...example Message String received below Message String Received STX 0 1 4 3 D A ACK ETX 5 6 Not included in calculation Message characters included Two byte ASCII checksum data field not included in ca...

Страница 11: ...rter MCN485CB2EOLT RS 485 cable up to 4000 ft Up to 32 units maximum PLC Controller Tone Generator 5540M 485Y6 or 5540MV 485Y6 Tone Generator 5540M 485Y6 or 5540MV 485Y6 9 RI 8 CTS 7 RTS 6 DSR 5 COM 4...

Страница 12: ...o Point Suggested Network Topology Node Schemes b a d c RS 485 Port RS 485 cable up to 4000 ft Tone Generator 5540M 485Y6 or 5540MV 485Y6 Tone Generator 5540M 485Y6 or 5540MV 485Y6 Up to 32 units maxi...

Страница 13: ...HIELD RS 485 BLACK RS 485 RED UNTERMINATED TERMINATED NOT A TELEPHONE CONNECTION RS 485 1 2 3456 1 NC 2 RS 485 3 SHIELD 4 NC 5 RS 485 6 NC RJ11 PINOUT TO IBM PC OR PLC RS 232 PORT TX RX TX RX RELAY RE...

Страница 14: ...separate power leads from signal and tone initiating leads Power and earth ground leads RS485 twisted pair Audio output wiring to be connected to Audio Coupler Board of 5532M Double wire shielded cab...

Страница 15: ...ER AUDIO COUPLER BOARDS A B MAIN BOARD POTENTIOMETER FOR VOLUME ADJUSTMENT AUDIO INPUT BOARD DIRECTION OF INCREASING VOLUME INPUT BOARD PROCESSOR BOARD MAIN BOARD POTENTIOMETER FOR VOLUME ADJUSTMENT I...

Страница 16: ...P N 3100346 ISSUE 3 PAGE 16 Figure 11 Connecting to the 5532B Series Speaker Amplifiers...

Страница 17: ...alternately 50 ms each for 1 2s 1 5s delay and repeat 13 Staircase 440 2000 Hz up and down steps 750 ms delay and repeat 14 3 Tone Alert 463 641 and 896 Hz 200 ms each 1 second delay and repeat 15 Pr...

Страница 18: ...7 1 98 24V AC 60 Hz 0 26 1 86 24V AC 50 Hz 0 26 1 86 5532BHV Y6 125V DC 0 05 0 25 250V DC 0 04 0 23 120V AC 60 Hz 0 10 0 62 240V AC 60 Hz 0 11 0 33 120V AC 50 Hz 0 09 0 62 240V AC 50 Hz 0 10 0 33 CE m...

Страница 19: ...ord button while speaking clearly into the microphone to record your message Release the button when recording is complete 4 To test the message press and hold PLAY while in programming mode NOTE This...

Страница 20: ...to both tone generator and 5532M series speaker amplifier except as noted If Edwards Signal Actuator catalog number 5538 4 is used to manually initiate tones connect its four normally open switches t...

Страница 21: ...opriate method of wiring to the input board from Figures 8 9 10 11 12 16 or 17 Connect the tone generator as shown d For 5532B AQ 5532BDV2 AQ and 5532BHV AQ models connect power source to the Speaker...

Страница 22: ...ies Tone Generator Plastic tie wrap provided use to separate power leads from signal and tone initiating leads Signal Tone initiating leads to be connected to Input Board Audio output wiring to be con...

Страница 23: ...K2 K1 ON INPUT BOARD Figure 10 Wiring Multiple Dry Contacts to 120V Tone Generator Input Board IN1 IN2 IN3 IN4 N VS GND K4 K3 K2 K1 120V AC ON INPUT BOARD NEUTRAL LINE Figure 8 Wiring an Open Collect...

Страница 24: ...TOR ONLY PROCESSOR BOARD TONE GENERATOR ONLY MAIN BOARD POTENTIOMETER FOR VOLUME ADJUSTMENT IN4 N VS GND PROGRAMMING SWITCHES ON OTHER SIDE IN1 IN2 IN3 VOICE BOARD SW 1 SW 2 SW 3 SW 4 DIRECTION OF INC...

Страница 25: ...Series Speaker Amplifiers Figure 17 Connecting from a PLC to 120V Tone Generator Input Board See Table 1 IN1 IN2 IN3 IN4 N VS GND VAC 1 OUT 0 OUT 1 OUT 2 OUT 3 VAC 2 OUT 1 OUT 2 OUT 3 OUT 4 OUT 5 OUT...

Страница 26: ...570 and 770 Hz alternately 50 ms each for 1 2s 1 5s delay and repeat 13 Staircase 440 2000 Hz up and down steps 750 ms delay and repeat 14 3 Tone Alert 463 641 and 896 Hz 200 ms each 1 second delay a...

Отзывы: