P/N 3100010 ISSUE 3
PAGE 9
Figure 19. Tone Programming
Switch
Tone
Description
1
2
3
4
5
HEX
No Tone
00
Ding-Dong
Percussive pairs of 700 and 570 Hz tones, each damped to zero
01
Warble
575 and 770 Hz alternately, 87 ms each
02
Siren
600-1250 Hz up and down sweep in 8 seconds and repeat
03
Stutter
Percussive 470 Hz, 83 ms on, 109 ms off
04
Slow Whoop
600-1250 Hz upward sweep in 4 seconds and repeat
05
Beep
470 Hz, 0.55 seconds on, 0.55 seconds off
06
Chime 1
700 Hz percussive repeat at 1 Hz
07
Fast Whoop
600-1250 Hz upward sweep in 1 second and repeat
08
Hi/Lo
780 to 600 Hz alternately, 0.52 seconds each
09
Rapid Siren
600-1250 Hz up and down sweep in 0.25 seconds and repeat
0A
Yeow
1250-600 Hz downward sweep in 1.6 seconds and repeat
0B
Horn
470 Hz continuous
0C
Air Horn
370 Hz continuous
0D
Dual Tone
450-500 Hz, 0.4 to 0.5 second cycle
0E
Chime 2
575 Hz percussive repeat at 1 Hz
0F
Westminster
Two measures, 411 Hz, 520 Hz, 407 Hz, 312 Hz
10
Three Blind Mice
Four measures, 787 Hz, 714 Hz, 625 Hz, 952 Hz, 333 Hz
11
Phasor
416-625 Hz up and down sweep in 13 ms and repeat
12
Telephone
570 and 770 Hz alternately, 50 ms each for 1.2s, 1.5s delay and repeat
13
Staircase
440-2000 Hz up and down steps, 750 ms delay and repeat
14
3 Tone Alert
463, 641 and 896 Hz, 200 ms each, 1 second delay and repeat
15
Presignal Chime
470 Hz percussive repeat at 1.5 Hz, followed by Message 1
16
Message 1
Field recorded voice message
17
Message 2
Field recorded voice message
18
Message 3
Field recorded voice message
19
Message 4
Field recorded voice message
1A
NFPA Whoop
Three 422-775 Hz upward sweeps, 850 ms each, 1s delay and repeat
1B
3 Pulse Horn
470 Hz, 3 0.5 second pulses separated by 0.5 seconds followed
1C
by a 1.5 second delay and repeat--
For Evacuation Use Only
3 Pulse Air Horn
370 Hz, 3 0.5 second pulses separated by 0.5 seconds followed
1D
by a 1.5 second delay and repeat--
For Evacuation Use Only
3 Pulse Dual Tone
450-500 Hz, 0.4 to 0.5 second cycle, 3 0.5 second pulses separated
1E
by 0.5 seconds followed by a 1.5 second delay and repeat--
For
Evacuation Use Only
3 Pulse Chime 2
575 Hz, 3 0.5 second pulses separated by 0.5 seconds followed
1F
by a 1.5 second delay and repeat--
For Evacuation Use Only
CAUTION
The use of evacuation signals on this product, that is not specifically Listed for
Fire Alarm Use, is subject to the approval of the Authority Having Jurisdiction.