23015-6-0408

Page 11

VENTING AND INSTALLATION

Vent System Approvals

Figure 8 

shows the vent termination caps and systems approved 

for  use  with  these  models. Approved  vent  system  terminations 

are  labeled  for  identification.  3-inch  diameter  listed  flexible 

aluminum or stainless steel gas vent is used for both the incoming 

combustion air and exhaust vent pipes. NO OTHER VENTING 

SYSTEMS  OR  COMPONENTS  MAY  BE  USED.  Detailed 

installation instructions are included with each vent termination 

kit and should be used in conjunction with this manual.

Horizontal Venting

The  vent  system  on  this  model 

CANNOT 

be  terminated 

horizontally.

Vertical Venting

The  inlet  and  exhaust  vent  pipes 

MUST 

be  connected  to  the 

proper collars on the unit 

AND 

to the termination cap or the unit 

will not operate. The intake vent collar is identified by a stamped 

“I” on the top collar sliding vent plate assembly.

WARNING: MAJOR U.S. BUILDING CODES SPECIFY 

MINIMUM  CHIMNEY  AND/OR  VENT  HEIGHT 

ABOVE THE ROOF TOP. THESE MINIMUM HEIGHTS 

ARE  NECESSARY  IN  THE  INTEREST  OF  SAFETY. 

SEE  FIGURES  8  THROUGH  10  FOR  MINIMUM 

HEIGHTS, PROVIDED THE TERMINATION CAP IS 

AT LEAST 2-FEET FROM A VERTICAL WALL AND 

2-FEET BELOW A HORIZONTAL OVERHANG.

Note: 

This also pertains to vertical vent systems installed on the 

outside of the building.

WARNING:  THE  EXHAUST  PIPE  MUST  ONLY 

BE  CONNECTED  TO  THE  EXHAUST  STARTING 

COLLAR  OF  THE  UNIT  AND  TO  THE  EXHAUST 

COLLAR OF THE TERMINATION CAP.
THE INLET AIR PIPE MUST ONLY BE CONNECTED 

TO  THE  INLET AIR  STARTING  COLLAR  OF  THE 

UNIT  AND  TO  THE  INLET  AIR  COLLAR  OF  THE 

TERMINATION CAP. BOTH THE INLET VENT AND 

THE  FLUE  VENT  MUST  BE  CONNECTED  FROM 

THE INSERT TO THE VENT TERMINATION CAP.

NOTE: 

The  minimum  vertical  vent  rise  is  10  feet  and  the 

maximum  vertical  vent  rise  is  35  feet.  These  dimensions  are 

measured from the starting collars of the unit to the end of the last 

section of vent pipe. 

See Figure 8.

NOTE: 

The  damper  of  the  masonry  chimney  may  need  to  be 

removed to allow installation of the flexible-vent pipe.
When installing into a zero clearance, factory built wood-burning 

fireplaces, the use of the DVKI Round Vertical Termination Kit 

should allow you to mount the vent adaptor and cap to the exposed  

round chimney pipe easily.

Connecting the Vent Pipe
Caution: Sharp edges. Always use gloves when installing.

Install the 3-inch flexible vent pipes down through the chimney.
Attach  the  pipe-to-cap  adaptor  to  the  termination  cap  and  the 

top of the flexible vent pipe, then install the cap to the top of the 

chimney. 
Remove the vent slide plate assembly from the top of the insert. 

See  Figure  7. 

Trim  off  excess  venting  then  attach  and  secure 

the bottom ends of the flex pipes to the starting collars with the 

adjustable band clamps provided. Slide the gas insert into place, 

and position any excess flex vent pipe back up into the chimney. 

Begin installation of the insert into the fireplace opening. Align 

the vent slide plate assembly with the guides located on top of 

the insert. Work the insert inch by inch into the fireplace cavity 

as you pull forward on the vent slide plate assembly. Do not use 

excessive force on the vent slide plate. Once the vent slide plate 

is close to seating, install the vent bolt through the center hole 

of the insert top flange, and into the vent slide plate nut. Using 

a wrench or socket, tighten the bolt until the vent slide plate is 

seated forward completely. 

Positioning, Leveling, and Securing Insert

1.  Place the insert into position.

Note:

 The front flanges of the insert (without surround panels) 

should be set at approximately 1”(inch) in front of the face of the 

fireplace.

2.  Level the insert from side to side and front to back.

3.  If necessary, use the leveling bolts included in the instruction 

pack. Screw the legs into the nuts installed in the bottom of 

the insert. Turn legs in until insert is level.

CAUTION: TO AVOID DOWNDRAFTS AND/OR COLD AIR 

PROBLEMS, IT IS RECOMMENDED TO SEAL OFF THE 

AREA BETWEEN THE TERMINATION CAP AND THE TOP 

OF THE SOLID-FUEL CHIMNEY OPENING INTO WHICH 

THE VENT CAP HAS BEEN INSTALLED.

Figure 7

Содержание DV25IN33L-1

Страница 1: ...iance is not convertible for use with other gases unless a certi ed kit is used GAS FIRED Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store...

Страница 2: ...10 12 Vertical Termination 13 Alternate ON OFF Switch Installation 14 Surround Panel Installation 15 Blower Accessory Information 16 Log Placement 17 Operating Instructions 18 Standing Pilot Lighting...

Страница 3: ...t clean Vent cap is hot while replace is in operation Installation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a quali...

Страница 4: ...perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wal...

Страница 5: ...ng jurisdiction State of Massachusetts The installation must be made by a licensed plumber or gas tter in the Commonwealth of Massachusetts The installation must conform with local codes or in the abs...

Страница 6: ...talling to an existing round replace chimney pipe DVVK3FV Vertical Vent Kit 25 Two pieces of 25 FlexVent Rectangle Cap Flashing connectors and clamps Recommended when installing to a square or rectang...

Страница 7: ...28 14 1 2 11 1 8 25 1 4 12 3 4 17 18 5 16 27 6 3 4 9 20 25 5 8 40 DV33IN 22 3 4 31 16 14 1 8 28 1 4 14 1 4 18 3 4 21 5 16 30 8 1 4 10 1 2 21 1 2 28 5 8 43 DV35IN 24 3 4 34 16 16 1 8 31 1 4 14 1 4 21 3...

Страница 8: ...10 1 3 4 23 11 Combustible Material No greeting cards stockings or ornamentation of any type should be placed on or attached to the replace The ow of heat can ignite combustibles Figure 4 8 MINIMUM CL...

Страница 9: ...s results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the replace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have a buil...

Страница 10: ...sting air circulation vents or grills NOTE Cutting of sheet metal parts of a replace in order to install the replace insert is prohibited WARNING Only the surround as supplied may be used to cover int...

Страница 11: ...asonry chimney may need to be removed to allow installation of the exible vent pipe When installing into a zero clearance factory built wood burning replaces the use of the DVKI Round Vertical Termina...

Страница 12: ...NT CONNECTION RETAINER SCREWS MAY BE INSTALLED THROUGH THE VENT CLAMPS TO ENSURE POSITIVE SECUREMENT OF VENTING SCREWS ADDED THROUGH VENT CLAMPS TO RETAIN VENTING TO COLLARS RECOMMENDED USE HIGH TEMP...

Страница 13: ...ly dripping out at joints or seams Condensate can cause corrosion of caps pipe and ttings It may be caused by having excessive lateral runs or having exterior portions of the system exposed to cold we...

Страница 14: ...ound panel assembly against the face of the insert and align the lower retaining tabs with the notches on the insert sides Lift the surround panel assembly slightly until the bottom return ange top pa...

Страница 15: ...FINISHING THE FIREPLACE INSERT NEVER OBSTRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE IN SERT IN ANY MANNER NOTE INSTALL SURROUND PANELS SO THAT THE TOP PANEL RETURN FLANGE SLIDE S OV...

Страница 16: ...nd BTU input level setting control by adjustment of the HI LO knob located on the gas valve Blower removal instructions Servicing or removal of the blower system must be performed by a quali ed servic...

Страница 17: ...support Note DV25IN models incorporate two small tabs in the rear log support that keep the back log positioned correctly DV33IN models have one small tab in the rear log support to ensure the back lo...

Страница 18: ...N position This time period allows the millivolts electrical current to build up to a suf cient level allowing the gas control to operate properly 1 Follow the SAFETY and LIGHTING INSTRUCTIONS for sta...

Страница 19: ...switch to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a re or explosion may result causing property damage personal injury or loss of l...

Страница 20: ...ptional Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8m or less length of 18 A W G minimum wire and connect it to the replace valve pigtails WARNIN...

Страница 21: ...s from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading atTH TP TPterminals...

Страница 22: ...that no debris is interfering with the ow of air Inspect entire vent system for proper function Cleaning Logs Use a soft brush attachment on a vacuum cleaner to gently remove dust or soot deposits fr...

Страница 23: ...what your dealer can furnish contact Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 Black Gold Finish Hammered Pewter Brushed Stainless Black Gold Finish Hammered Pewt...

Страница 24: ...23015 6 0408 Page 24 INSERT PARTS VIEW 1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 19 20 21 22 23 24 25 26 27 28 29 30 31 33 34 35 36 37 38 39 40 41 7 12 32 42 43 18 44 45 46 48 47 49...

Страница 25: ...23a P286 P270 P244 ORIFICE MAIN BURNER NAT 23b P214 P210 P245 ORIFICE MAIN BURNER LP 24 23311 23017 23017 BURNER ASSEMBLY 25 22959 22959 22959 VALVE BRACKET 26 22739 22738 22738 TUBING ASSEMBLY 27 22...

Страница 26: ...ne the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Fireplace Number Part Description Fir...

Страница 27: ...23015 6 0408 Page 27 SERVICE NOTES...

Страница 28: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: