Vertical Through the Roof Applications

The Gas Fireplace Insert has been approved for:

a)  Vertical installations up to 35 feet in height (top of insert to 

cap).

b)  Two sets of 45 degree elbow offsets (bends in flexvent) within 

the vertical installation. From 0 to a maximum of 8 ft. of vent 

pipe can be used between elbows.

c)  Wall straps must be used to support offset pipe every 4'. 
This application will require that you first determine the roof pitch 

and use the appropriate venting components.

General Maintenance

Conduct  an  inspection  of  the  venting  system  semi-annually. 

Recommended areas to inspect are as follows:

1.  Check areas of the venting system which are exposed to the 

elements  for  corrosion.  These  will  appear  as  rust  spots  or 

streaks and, in extreme cases, holes. These components should 

immediately be replaced.

2.  Remove the cap and shine a flashlight down the vent. Remove 

any bird nests or other foreign material.

3.  Check  for  evidence  of  excessive  condensate,  such  as  water 

droplets forming in the flex venting and subsequently dripping 

out at joints or seams. Condensate can cause corrosion of caps, 

pipe and fittings. It may be caused by having excessive lateral 

runs, or having exterior portions of the system exposed to cold 

weather.

4.  Inspect joints to verify that no pipe sections or fittings have been 

disturbed and, consequently, loosened. Also, check mechanical 

supports, such as wall straps or plumbers’ tape for rigidity. 

Determining Minimum Vent Height Above the Roof.
WARNING:  Major  U.S.  building  codes  specify  minimum 

chimney and/or vent height above the roof top. These minimum 

heights are necessary in the interest of safety. These specifica-

tions are summarized in Figure 9.

Figure 9

Note that for steep roof pitches, the vent height must be increased. 

In high wind conditions, nearby trees, adjoining roof lines, steep 

pitched roofs, and other similar factors can result in poor draft, 

or down-drafting. In these cases, increasing the vent height may 

solve this problem.

When terminating the vent cap near an exterior wall or overhang, 

maintain minimum clearances as shown in 

Figure 10.

ROOF PITCH

H (Min.)

Flat to 6/12

12" (305 mm)

6/12 to 7/12

15" (381 mm)

Over 7/12 to 8/12

18" (457 mm)

Over 8/12 to 16/12

24" (610 mm)

Over 16/12 to 21/12

36" (914 mm)

VERTICAL TERMINATION

Figure 10

MIN.

12" MIN.

24"

24"

MIN.

CL

Содержание DV25IN33L-1

Страница 1: ...iance is not convertible for use with other gases unless a certi ed kit is used GAS FIRED Installer Leave this manual with the appli ance Consumer Retain this manual for future refer ence Do not store...

Страница 2: ...10 12 Vertical Termination 13 Alternate ON OFF Switch Installation 14 Surround Panel Installation 15 Blower Accessory Information 16 Log Placement 17 Operating Instructions 18 Standing Pilot Lighting...

Страница 3: ...t clean Vent cap is hot while replace is in operation Installation and repair should be done by a QUALIFIED SERVICE PERSON The appliance should be inspected before use and at least annually by a quali...

Страница 4: ...perform service or make adjustments in an area where the conditions are such that you may not detect the odor if there has been a leak of LP Gas Odor fade due to oxidation by rust or adsorption on wal...

Страница 5: ...ng jurisdiction State of Massachusetts The installation must be made by a licensed plumber or gas tter in the Commonwealth of Massachusetts The installation must conform with local codes or in the abs...

Страница 6: ...talling to an existing round replace chimney pipe DVVK3FV Vertical Vent Kit 25 Two pieces of 25 FlexVent Rectangle Cap Flashing connectors and clamps Recommended when installing to a square or rectang...

Страница 7: ...28 14 1 2 11 1 8 25 1 4 12 3 4 17 18 5 16 27 6 3 4 9 20 25 5 8 40 DV33IN 22 3 4 31 16 14 1 8 28 1 4 14 1 4 18 3 4 21 5 16 30 8 1 4 10 1 2 21 1 2 28 5 8 43 DV35IN 24 3 4 34 16 16 1 8 31 1 4 14 1 4 21 3...

Страница 8: ...10 1 3 4 23 11 Combustible Material No greeting cards stockings or ornamentation of any type should be placed on or attached to the replace The ow of heat can ignite combustibles Figure 4 8 MINIMUM CL...

Страница 9: ...s results in pressures in excess of 1 2 psig 14 w c 3 5 kPa on the replace gas valve it will result in a hazardous condition Checking Manifold Pressures Both Propane and Natural gas valves have a buil...

Страница 10: ...sting air circulation vents or grills NOTE Cutting of sheet metal parts of a replace in order to install the replace insert is prohibited WARNING Only the surround as supplied may be used to cover int...

Страница 11: ...asonry chimney may need to be removed to allow installation of the exible vent pipe When installing into a zero clearance factory built wood burning replaces the use of the DVKI Round Vertical Termina...

Страница 12: ...NT CONNECTION RETAINER SCREWS MAY BE INSTALLED THROUGH THE VENT CLAMPS TO ENSURE POSITIVE SECUREMENT OF VENTING SCREWS ADDED THROUGH VENT CLAMPS TO RETAIN VENTING TO COLLARS RECOMMENDED USE HIGH TEMP...

Страница 13: ...ly dripping out at joints or seams Condensate can cause corrosion of caps pipe and ttings It may be caused by having excessive lateral runs or having exterior portions of the system exposed to cold we...

Страница 14: ...ound panel assembly against the face of the insert and align the lower retaining tabs with the notches on the insert sides Lift the surround panel assembly slightly until the bottom return ange top pa...

Страница 15: ...FINISHING THE FIREPLACE INSERT NEVER OBSTRUCT OR MODIFY THE AIR INLET OUTLET LOUVERS ON THE FIREPLACE IN SERT IN ANY MANNER NOTE INSTALL SURROUND PANELS SO THAT THE TOP PANEL RETURN FLANGE SLIDE S OV...

Страница 16: ...nd BTU input level setting control by adjustment of the HI LO knob located on the gas valve Blower removal instructions Servicing or removal of the blower system must be performed by a quali ed servic...

Страница 17: ...support Note DV25IN models incorporate two small tabs in the rear log support that keep the back log positioned correctly DV33IN models have one small tab in the rear log support to ensure the back lo...

Страница 18: ...N position This time period allows the millivolts electrical current to build up to a suf cient level allowing the gas control to operate properly 1 Follow the SAFETY and LIGHTING INSTRUCTIONS for sta...

Страница 19: ...switch to desired setting FOR YOUR SAFETY READ BEFORE LIGHTING WARNING If you do not follow these instructions exactly a re or explosion may result causing property damage personal injury or loss of l...

Страница 20: ...ptional Wall Switch Position the wall switch in the desired position on a wall Run a maximum of 25 feet 7 8m or less length of 18 A W G minimum wire and connect it to the replace valve pigtails WARNIN...

Страница 21: ...s from the thermopile at the gas valve terminals are tight and the thermopile is fully inserted into the pilot bracket Check the thermopile with a millivolt meter Take the reading atTH TP TPterminals...

Страница 22: ...that no debris is interfering with the ow of air Inspect entire vent system for proper function Cleaning Logs Use a soft brush attachment on a vacuum cleaner to gently remove dust or soot deposits fr...

Страница 23: ...what your dealer can furnish contact Empire Comfort Systems Inc Nine Eighteen Freeburg Ave Belleville Illinois 62220 Black Gold Finish Hammered Pewter Brushed Stainless Black Gold Finish Hammered Pewt...

Страница 24: ...23015 6 0408 Page 24 INSERT PARTS VIEW 1 2 3 4 5 6 7 8 9 10 11 13 14 15 16 17 19 20 21 22 23 24 25 26 27 28 29 30 31 33 34 35 36 37 38 39 40 41 7 12 32 42 43 18 44 45 46 48 47 49...

Страница 25: ...23a P286 P270 P244 ORIFICE MAIN BURNER NAT 23b P214 P210 P245 ORIFICE MAIN BURNER LP 24 23311 23017 23017 BURNER ASSEMBLY 25 22959 22959 22959 VALVE BRACKET 26 22739 22738 22738 TUBING ASSEMBLY 27 22...

Страница 26: ...ne the Part Number not the Index Number and the Description of each part from the following appropriate illustration and list Be sure to give all this information Fireplace Number Part Description Fir...

Страница 27: ...23015 6 0408 Page 27 SERVICE NOTES...

Страница 28: ...s Empire Comfort Systems Inc 918 Freeburg Ave Belleville IL 62220 If you have a general question about our products please e mail us at info empirecomfort com If you have a service or repair question...

Отзывы: